8 Configuration
a
[F-03]
b
T
A
[F-02]
T
Outdoor temperature
A
a
On
b
OFF
CAUTION
The bottom plate heater is controlled via EKRP1HB.
#
Code
N/A
[F-02]
Bottom plate heater ON temperature:
3°C~10°C (default: 3°C)
N/A
[F-03]
Hysteresis: 2°C~5°C (default: 5°C)
INFORMATION
Depending on setting [F-04], contact Y2, located on digital
I/O PCB EKRP1HB, controls the optional bottom plate
heater. See the illustration below for the schematic location
of this contact. For the complete wiring, see the wiring
diagram.
X2M
X1M
YC Y1
Y2
Y3 Y4
8.3.4

System settings

Priorities
#
Code
N/A
[5-02]
Space heating priority.
Defines whether domestic hot water is
made by booster heater only when
outdoor temperature is below space
heating priority temperature. It is
recommended to enable this function to
shorten tank heating operation time
and guaranteed domestic hot water
comfort.
▪ 0: disabled
▪ 1: enabled
[5‑01] Equilibrium temperature and
[5‑03] Space heating priority
temperature are related to backup
heater. So, you must set [5‑03] equal or
a few degrees higher than [5‑01].
N/A
[5-03]
Space heating priority temperature.
Defines the outdoor temperature which
below the domestic hot water will be
heated by booster heater only.
Range: –15°C~35°C (default: 0°C).
Installer reference guide
68
Description
OFF ON
SS1
Description
#
Code
N/A
[5-04]
Set point correction for domestic hot
water temperature: set point correction
for the desired domestic hot water
temperature, to be applied at low
outdoor temperature when space
heating priority is enabled. The
corrected (higher) set point will make
sure that the total heat capacity of the
water in the tank remains
approximately unchanged, by
compensating for the colder bottom
water layer of the tank (because the
heat exchanger coil is not operational)
with a warmer top layer.
Range: 0°C~20°C (default: 10°C).
N/A
[C-00]
If a solar kit is installed, what has
priority to heat up the tank?
▪ 0: Solar kit
▪ 1: Heat pump
Auto-restart
When power returns after a power supply failure, the auto restart
function reapplies the remote controller settings at the time of the
power failure. Therefore, it is recommended to always enable the
function.
If the preferential kWh rate power supply is of the type that power
supply is interrupted, always enable the auto restart function.
Continuous indoor unit control can be guaranteed independent of the
preferential kWh rate power supply status, by connecting the indoor
unit to a normal kWh rate power supply.
#
Code
[A.6.1]
[3‑00]
Is the auto restart function of the unit
allowed?
▪ 0: No
▪ 1 (default): Yes
Preferential kWh rate power supply
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/3+4) as the safety
thermostat. It is only possible for the system to have
EITHER preferential kWh rate power supply OR a safety
thermostat.
ERLQ004~008CA + EHVH04+08SU18+26CB6W
Description
Description
Daikin Altherma – Low temperature split
4P449978-1B – 2018.07