Lenovo RT5.0kVA Installation And User Manual page 58

3u rack or tower ups
Table of Contents

Advertisement

Table 9. Electrical output (continued)
All models
Frequency regulation
Frequency
Output overload
Output overload (Bypass
mode)
Voltage waveform
Harmonic distortion
Transfer time
Power factor
Load crest ratio
Table 10. Electrical output connections
Model
5594-5KX
5594-6KX
Table 11. AC input and output
AC Input power
AC Output power
46
3U Rack or Tower UPS RT5.0kVA and RT6.0kVA Installation and User's Guide
Normal mode
Sync with line ±5% of nominal line frequency
(outside this range: ±0.5% of auto-selected
nominal frequency)
50 or 60Hz, autosensing or configurable as a frequency converter
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150% : load transfers to Bypass mode after 500ms
100-125% : no alarm
125-150% : UPS shuts down after 1 minute
> 150% : UPS shuts down after 1s
Sinewave
< 2% THDV on linear load
< 5% THDV on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
0.9
3 to 1
Output connection
Hardwired
(2) IEC 16A
(4) IEC 10A group 1
(4) IEC 10A group 2
5594-5KX
200-240VAC, 50/60Hz, 1ph, 25A max
50/60Hz, 1ph;
200VAC, 5000VA, 4500W, 25.0A;
208VAC, 5000VA, 4500W, 24.0A;
220VAC, 5000VA, 4500W, 22.7A;
Battery mode
±0.5% of auto-selected nominal
frequency
Output cable
(2) IEC 10A
5594-6KX
200-240VAC, 50/60Hz, 1ph, 30A max
50/60Hz, 1ph;
200VAC, 6000VA, 5400W, 30.0A;
208VAC, 6000VA, 5400W, 28.8A;
220VAC, 6000VA, 5400W, 27.3A;