Application guidelines
6.6.1 Permanent power limitation
Installer reference guide
60
#
2
"6.6.2 Power limitation activated by digital
▪
Allows you to limit the power consumption of the entire heat pump
system (sum of indoor unit and backup heater) via 4 digital inputs.
▪
Limitation of power in kW or current in A.
3
"6.6.4 BBR16 power
▪
Restriction: Only available in Swedish language.
▪
Allows you to comply with BBR16 regulations (Swedish energy
regulations).
▪
Limitation of power in kW.
▪
Can be combined with the other kW power consumption controls. If you
do so, the unit uses the most restrictive control.
NOTICE
It is possible to install a field fuse with lower than recommended rating over the heat
pump. For this you must modify field setting [2‑0E] according to the maximum
allowed current over the heat pump.
Note that field setting [2‑0E] overrules all power consumption control settings.
Power limiting the heat pump will reduce performance.
NOTICE
Set a minimum power consumption of ±3.6 kW to guarantee:
▪
Defrost operation. Otherwise, if defrosting is interrupted several times, the heat
exchanger will freeze up.
▪
Space heating and DHW production by allowing the backup heater step 1.
▪
Anti-legionella operation.
Permanent power limitation is useful to assure a maximum power or current input
of the system. In some countries, legislation limits the maximum power
consumption for space heating and DHW production.
P
i
a
DI
P
Power input
i
t Time
DI Digital input (power limitation level)
a Power limitation active
b Actual power input
Setup and configuration
▪
No additional equipment needed.
Power consumption control
4
limitation" [
63]
b
t
4
inputs" [
61]
EPRA08~12EAV3+W1 + ETBH/X12EF6V+9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03