11.5. Field setting list for Operation Manual

First
Second
code
code
Setting name
Remote control setup
0
00
Installation related setting
01
Installation related setting
02
Not applicable. Do not change the default value.
03
Status: space heating schedule timer mode
Method 1=1 / Method 2=0.
04
Status: space cooling schedule timer mode
Method 1=1 / Method 2=0.
1
Settings are not applicable
00
Not applicable. Do not change the default value.
01
Not applicable. Do not change the default value.
02
Not applicable. Do not change the default value.
03
Not applicable. Do not change the default value.
2
Automatic setback function
00
Status: setback operation.
01
Setback operation start time.
02
Setback operation stop time.
Weather dependent set point
3
00
Low ambient temperature (Lo_A).
01
High ambient temperature (Hi_A).
02
Set point at low ambient temperature (Lo_Ti).
03
Set point at high ambient temperature (Hi_Ti).
Settings are not applicable
4
00
Not applicable. Do not change the default value.
01
Not applicable. Do not change the default value.
02
Not applicable. Do not change the default value.
5
Automatic setback and disinfection set point
00
Not applicable. Do not change the default value.
01
Not applicable. Do not change the default value.
02
Leaving water setback temperature.
03
Room setback temperature.
04
Not applicable. Do not change the default value.
6
Option setup
01
Installation related setting
02
Installation related setting
03
Not applicable. Do not change the default value.
8
Option setup
00
Installation related setting
01
Not applicable. Do not change the default value.
02
Emergency operation.
03
Not applicable. Do not change the default value.
04
Installation related setting
9
Automatic temperature compensation
00
Installation related setting
01
Installation related setting
02
Not applicable. Do not change the default value.
03
Installation related setting
04
Not applicable. Do not change the default value.
Installation and operation manual
38
Installer setting at variance with default value
Date
(a)
(a)
(a)
(a)
(a)
(a)
(a)
(a)
(a)
Value
Date
Value
Default
value
Range
Step
2
2~3
1
0
–5~5
0.5
1
1 (ON)
0/1
1 (ON)
0/1
1
1:00
0
15:00
1 (ON)
0/1
23:00
0:00~23:00
1:00
5:00
0:00~23:00
1:00
–10
–20~5
1
15
10~20
1
40
25~80
1
25
25~80
1
1
Fri
23:00
70
10
5
0~10
1
18
17~23
1
0
0 (OFF)
0/2
0 (OFF)
0/1
0
1 (ON)
0/1
1
0
0/1
1
0
0~2
1
0
–2~2
0.2
1 (ON)
0/1
1
0
0
–2~2
0.2
0
HXY080+125A8V1BF
VRV IV System indoor unit
4P405267-1C – 2021.04
Unit
°C
hour
hour
°C
°C
°C
°C
°C
°C
°C
°C