Air to Water Heat Pump (Split integrated DHW type)
2 .7 .3 Additional charge
The charge in the outside units corresponds to the maximum distances between the outside unit and the hydraulic
module defined in
page
charge depends on the distance between the outside unit and the hydraulic module for each type of appliance.
The additional charge of R410A must necessarily be made by an approved refrigeration engineer.
7.5m < Length of the connections ≤ 15m
[0.03 x (Length of the connections - 7.5) + 0.175] x 1000 = g
If the temperature control set on the hydraulic module is less than or equal to 0.4, an additional charge must be
added from 5m refrigerant piping according to the formula: 0.03 x (length of the connections - 5) + 0.1.
Length of the
8
connections m
Charge
g
1290
Length of the
11
connections m
Charge
g
1470
7.5m < Length of the connections ≤ 15m
[0.04 x (Length of the connections - 7.5)] x 1000 = g
Length of the
10
connections m
Charge
g
1900
- 22 -
18. For some distances, an additional charge of R410A is required. The additional
extensa + 5, 6 (Outdoor unit WOYA060LDC)
Comfort 5, 6
9
10
11
1320
1350
1380
1410
extensa + 8 (Outdoor unit WOYA080LDC)
Comfort 8
7.5m < Length of the connections ≤ 20m
[0.02 x (Length of the connections - 7.5)] x 1000 = g
12
13
1490
1510
1530
Comfort 10
extensa + 10 (Outdoor unit WOYA100LDT)
11
12
13
1940
1980
2020
15m < Length of the connections ≤ 20m
[0.02 x (Length of the connections - 15) + 0.4] x 1000 = g
12
13
14
15
1440
1470
1500
14
15
16
1550
1570
15m < Length of the connections ≤ 20m
[0.05 x (Length of the connections - 15) + 0.3] x 1000 = g
14
15
2060
2100
2150
16
17
18
1520
1540
1560
17
18
1590
1610
16
17
18
2200
2250
Installation and operating manual "1585 - EN"
19
20
1580
1600
19
20
1630
1650
19
20
2300