OPERATING PROCEDURE
7. Removing the line flow fan, the indoor fan motor
assembly, the indoor coil thermistor (Photo 10,
11, 12)
(1) Remove the front panel, the horizontal vanes (U) (L),
the panels (R) (L) (F) (U), the Wi-Fi interface, the elec-
trical box, and the nozzle assembly.
(2) Disengage the catches of the water cover, and remove
the water cover.
(3) Loosen the screw inside the right side of the line flow
fan (Photo 10).
(4) Remove the 3 screws of the fan motor assembly. Pull
the fan motor assembly slightly toward you, and
remove it by pulling to the right (Photo 11).
(5) Remove the indoor coil thermistor from the heat
exchanger.
(6) Remove the 2 screws of the hairpin holder on the left
side of the heat exchanger. Raise the left side of the
heat exchanger, and pull the line flow fan to the lower
left to remove (Photo 12).
*1 When attaching the line flow fan, screw the line flow
fan so 4 mm gap is provided between the right end of
the line flow fan and the right wall of the air passage of
the box (Figure 2).
Figure 2
4 mm
OBH930
PHOTOS/FIGURES
Photo 10
Heat exchanger
Screw of the line flow fan
Photo 11
Photo 12
Hairpin holder
Screw of the left side of the heat exchanger
46
Fan motor
Screws of
the fan motor