Mitsubishi Electric MSZ-AY25VGKP-E6 Service Manual page 27

Table of Contents

Advertisement

2. Flow chart of AIR PURIFYING power failure mode recall function (MSZ-AY•VGKP)
Operational procedure
The air purifying device might be abnormal.
Check if the air purifying device is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TEMP
TEMP
button to adjust the set temperature to 23 °C. *1
Does POWER lamp on the indoor unit blink
at the interval of 0.5 seconds?
Blinks: The air purifying device is abnormal.
Beep is emitted at the same timing as the
blinking of POWER lamp. *2
The air purifying device is abnormal.
Check the blinking pattern, and identify the abnormal point with the table of
AIR PURIFYING power failure mode recall function (10-2.5.).
Make sure to check at least 2 consecutive blinking cycles. *2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
Press OFF/ON (stop/operate) button of the remote controller (the set temperature is displayed) with the remote
controller headed towards the indoor unit.
Press the emergency operation switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Note 1: Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
Note 2: If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
*2. Blinking pattern when the air purifying device is abnormal:
2.5-second OFF
ON
OFF
Repeated cycle
3. AIR PURIFYING power operation check
AIR PURIFYING power operation goes ON when PURIFIER button on the remote controller is pressed
with any set temperature displayed during failure mode recall function.
Check the operation display section of the remote controller to confirm that AIR PURIFYING power operation is activated.
While AIR PURIFYING lamp stays OFF, it means normal.
Blinking AIR PURIFYING lamp means abnormal, the AIR PURIFYING power operation is not conducted.
AIR PURIFYING lamp
Continuously blinking
Follow "Check of AIR PURIFYING power" to identify the error. (Refer to 10-6. .)
AIR PURIFYING power control circuit on the indoor electronic control P.C. board is out of order.
2-time blink
(Refer to 10-6. .)
NOTE: Perform the above mentioned check with the front panel closed. The interlock switch (Air purifying device) works by
opening front panel and the AIR PURIFYING power is cut.
OBH930
Yes
(Blinks)
Repair the failure parts.
Blinking at 0.5-
second interval
2.5-second OFF
Beeps
Repeated cycle
or
*1. Regardless of normal or abnormal condition,
a short beep is emitted as the signal is received.
No
(OFF)
Release the failure mode recall function according to
the left mentioned procedure.
Blinking at 0.5-
second interval
Beeps
Repeated cycle
Remedy
27
The air purifying device is normal.
Beeps

Advertisement

Table of Contents
loading

Table of Contents