4 Set-up
Quantity
Description
1
Gas pipe
1
Expansion relief valve discharge pipe
1
Installation template
1
Enclosed documentation
4.4
Dimensions
1
123
185
220
1
Heating flow
2
Gas connection
3
Heating return
8
2
3
123
390
150
4
5
4
Connection on the back
of the air/flue pipe
5
Connection on the top
of the air/flue pipe
4.5
Minimum clearances
C
C
A
B
C
(70 mm, if the side sections have to be removed)
D
4.6
Clearance from combustible components
It is not necessary to maintain a clearance between the
product and components made of combustible materials that
go beyond the minimum clearances .
4.7
Using the mounting template
▶
Use the mounting template to ascertain the locations at
which you need to drill holes.
4.8
Wall-mounting the product
Note
If you are using the rear air/flue connection, in-
stall the air/flue pipe before you wall-mount the
product.
1.
Check whether the wall has sufficient load-bearing ca-
pacity to bear the operational weight of the product.
2.
Check if the supplied fixing material may be used for
the wall.
Installation and maintenance instructions ecoFIT sustain 0020277252_00
D
Minimum clearance
150 mm (top air/flue gas connection)
20 mm (rear air/flue connection)
150 mm
600 mm
5 mm