3. Horizontal left-flow
Horizontal left-flow is another default factory configuration for the units. These units may be
converted to horizontal left-flow by removing indoor coil assembly with drain pan and reinstalling it
as shown below.
Rotate the unit 90° into the horizontal left position, with the coil compartment on the right and the
blower compartment on the left.
Reinstall the indoor coil 180° from original position. Ensure the retaining channel is fully engaged
with the coil rail(Figure 3-4 and 3-5).
Aftermarket drain pan kits are required when the unit is configured for the horizontal position over
a finished ceiling and living space.
A
1 4
AIRFLOW
Figure 3-4 Horizontal left-flow application
11
ENSURE THE RETAINNG CHANNEL IS FULLY
ENGAGED WITH THE COIL RAIL.
DETAIL
RAILS
RAILS