Lgt/Lct102H - Lennox LGT092H Installation Instructions Manual

Hide thumbs Also See for LGT092H:
Table of Contents

Advertisement

65 F
Suct
Disc
(psig)
(psig)
109
228
117
231
Circuit 1
133
239
151
250
124
243
132
249
Circuit 2
150
261
170
271
Circuit 1
120
Circuit 2
110
100
90
80
70
60
100
110
TABLE 5 581115-01
LGT/LCT102
Normal Operating Pressures
Outdoor Coil Entering Air Temperature
75 F
85 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
111
266
114
119
267
122
137
272
140
155
280
159
126
280
128
134
285
136
153
294
155
173
301
176
Charging Curves
120
130
Suction Pressure (psig)
95 F
Disc
Suct
Disc
(psig)
(psig)
(psig)
312
116
362
312
125
363
314
143
366
319
163
373
327
130
383
331
139
385
337
158
388
341
179
390
75°
65°
140
150
Page 21
105 F
Suct
Disc
(psig)
(psig)
(psig)
118
430
127
427
146
423
166
423
132
448
142
449
161
449
183
448
Outdoor Temperature (°F)
115°
105°
95°
85°
160
170
180
115 F
Suct
Disc
(psig)
119
502
129
497
148
490
169
487
135
523
144
522
164
520
186
515
190

Hide quick links: