To Determine If Oil Traps Are Required; Checking The Refrigerant Piping; About Checking The Refrigerant Piping - Daikin Siesta AZQS125B8V1B Installer's Reference Manual

Hide thumbs Also See for Siesta AZQS125B8V1B:
Table of Contents

Advertisement

6 Installation
INFORMATION
a
b
b
▪ Remove the knockout hole (a) in the bottom plate or
cover plate by tapping on the attachment points with a
flat head screwdriver and a hammer.
▪ Optionally, cut out the slits (b) with a metal saw.
NOTICE
Precautions when making knockout holes:
▪ Avoid damaging the casing and underlying piping.
▪ After making the knockout holes, we recommend to
remove the burrs and paint the edges and areas
around the edges using repair paint to prevent rusting.
▪ When passing electrical wiring through the knockout
holes, wrap the wiring with protective tape to prevent
damage.
3 Do the following:
▪ Connect the liquid pipe (a) to the liquid stop valve.
▪ Connect the gas pipe (b) to the gas stop valve.
b
a
4 Do the following:
▪ Insulate the liquid piping (a) and the gas piping (b).
▪ Wind heat insulation around the curves, and then cover it
with vinyl tape (c).
▪ Make sure the field piping does not touch any compressor
components (d).
▪ Seal the insulation ends (sealant etc.) (e).
f
d
5 If the outdoor unit is installed above the indoor unit, cover the
stop valves (f, see above) with sealing material to prevent
condensed water on the stop valves from moving to the indoor
unit.
NOTICE
Any exposed piping might cause condensation.
6 Reattach the service cover and the piping intake plate.
7 Seal all gaps (example: a) to prevent snow and small animals
from entering the system.
Installer reference guide
14
b
a
b
e
a
b
c
a
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
NOTICE
Make sure to open the stop valves after installing the
refrigerant piping and performing vacuum drying. Running
the system with the stop valves closed may break the
compressor.
6.4.9

To determine if oil traps are required

If oil flows back into the outdoor unit's compressor, this might cause
liquid compression or deterioration of oil return. Oil traps in the rising
gas piping can prevent this.
If
The indoor unit is installed
Install an oil trap every 10 m (height
higher than the outdoor
difference).
unit
a Rising gas piping with oil trap
b Liquid piping
The outdoor unit is
Oil traps are NOT required.
installed higher than the
indoor unit
6.5

Checking the refrigerant piping

6.5.1

About checking the refrigerant piping

The outdoor unit's internal refrigerant piping has been factory tested
for leaks. You only have to check the outdoor unit's external
refrigerant piping.
Before checking the refrigerant piping
Make sure the refrigerant piping is connected between the outdoor
unit and the indoor unit.
Typical workflow
Checking the refrigerant piping typically consists of the following
stages:
1
Checking for leaks in the refrigerant piping.
2
Performing vacuum drying to remove all moisture, air or
nitrogen from the refrigerant piping.
AZQS100~140B8V1B + AZQS100~140B7Y1B
Then
a
10 m
b
Split system air conditioners
4P385529-1C – 2019.04

Advertisement

Table of Contents
loading

Table of Contents