3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Table 3–2: TYPES OF FILES CREATED BY ENERVISTA 650 SETUP– ONLINE OPERATION MODE
SETTINGS & CONFIGURATION FILE *.650
Description
Protection Settings and Configuration Section
Created by
EnerVista 650 Setup
Relay
configuration
elements, settings, input/output and LEDs configuration,
Contents
graphic display configuration, etc.
Equations corresponding to the logic created and
compiled in the PLC Editor
Connect with the relay ("Communications>Computer") Connect with the relay ("Communications>Computer")
How to
Send settings and configuration from file
transfer to
relay
Modify settings and configuration directly in the relay:
EnerVista 650 Setup:
How to save
"File>Get info from relay". User definable texts
retrieved are operations, events, and LEDs.
How to store in the relay
How to retrieve from the relay
Logic programming support files (*.pep, *.aut, *.lib) CANNOT be retrieved directly from the relay.
It is necessary
* Either to have stored these files in the PC
* Or to have uploaded previously the files into the relay ("Communication>Upload info files to relay")
GEK-113328A
file
containing
all
protection
REMINDER:
G650 Generator Protection & Control System
LOGIC CONFIGURATION FILES (*.PEP, *.AUT, *.LIB)
*.PEP
*.AUT
Graphical edition
container. Logic
Header for Logic
equations (Virtual
project
Outputs) in FDB
format.
Logic configuration
Logic configuration
graphic editor (PLC
graphic editor (PLC
Editor)
Editor)
PLC project file
PLC Project file
containing the
containing all the
necessary
drawings used by
information relative
the logic, required
to the relay model,
by 650 relay based
logic libraries
on IEC 61131-3
included in the
standard.
project (*.lib),
Functional block
graphic file name
diagram (FDB).
(*.aut), etc.
Launch 650 Logic equations editor ("Setpoint>Logic
Configuration")
Open the created PLC project ("File>Open Project")
Compile the project ("Run>Compile")
Now the logic (virtual outputs) can be sent directly to relay
("Run>Send Equations to Relay"). Texts of virtual outputs are
not stored in the relay, only in the logic configuration files to be
edited.
PLC Editor:
"File>Save Project"
The relay will not
The relay will not
provide this
provide this
information unless
information unless
the *.pep file is
the *.pep file is
stored in the relay
stored in the relay.
To store the logic configuration files in the relay use the
"Communication>Upload info files to relay" option
"Communication>Upload info files to relay" through Ethernet
"Communication/Download info files from relay" through
Ethernet
*.LIB
User programmable
logic objects
Logic configuration
graphic editor (PLC
Editor)
Library file to be
included as an object
in a PLC project.
3
Logic packages that
can be stored into
libraries and be
distributed in different
PLC projects.
"File>Save Library"
The relay will not
provide this
information unless
the *.pep file is stored
in the relay.
3-9