B.1 FACTORY DEFAULT SETTINGS
SETPOINT > CONTROL ELEMENTS > ACCIDENTAL ENERGIZATION
ACCIDENTAL ENERGIZATION 1 > ACCIDENTAL ENERGIZATION 2 > ACCIDENTAL ENERGIZATION 3
SETTING DESCRIPTION
Function Permission
Arming mode for Accidental
Energization
Overcurrent Level to operate
B
Arming undervoltage value
Snapshot Event generation
B-18
NAME
DEFAULT VALUE
Function
DISABLED
Accdnt Enrg Mode
UV AND OFF-LINE N/A
Overcurrent pickup
1.50
Ph Undervoltage
40.00
pickup
Snapshot Events
ENABLED
G650 Generator Protection & Control System
STEP
RANGE
N/A
[DISABLED – ENABLED]
[UV AND OFF-LINE – UV
OR OFF-LINE]
0.01 A
[0.00 : 160.00]
0.01 V
[0.00 : 500.00]
N/A
[DISABLED – ENABLED]
APPENDIX B
USER
VALUE
GEK-113328A