Commissioning; User Profile; Operation - Daikin ERRA08-12EW1 Installer's Reference Manual

Table of Contents

Advertisement

11.6.10 Commissioning

11.6.11 User profile

11.6.12 Operation

ERRA08~12E + ELVH/X12S18+23E
Daikin Altherma 3 R MT F
4P708474-1 – 2023.05
Main zone pump fixed PWM
The speed of the main zone pump can be fixed with this setting.
#
Code
[9.P.4]
[7-0B]
Mixing valve turning time
If a third party mixing valve is installed in combination with controller EKMIKPOA,
the valve turning time must be set accordingly.
For this setting, space heating/cooling and tank operation MUST be off:
[C.2]  Space
heating/cooling=0  (Off) and [C.3]  Tank=0  (Off). See
4
"11.6.12 Operation" [
 249].
#
Code
[9.P.5]
[7-0C]
Overview
The following items are listed in the submenu:
A
Information
Installer settings

Commissioning

User profile

Operation

About commissioning
See: "12 Commissioning" [
[B] User profile: See
B
Installer settings
Commissioning
User profile
Operation
Malfunctioning
Overview
The following items are listed in the submenu:
Main zone pump fixed PWM: Fixed pump
speed for main (mixed) zone.
20~95% (default: 95)
Mixing valve turning time: Time in
seconds for the mixing valve to turn from one
side to the other.
20~300 sec (default: 125)
[A] Commissioning
[A.1] Operation test run
[A.2] Actuator test run
[A.3] Air purge
[A.4] UFH screed dryout
4
 256]
"To change the user permission
[B] User profile
11
Configuration
|
Description
Description
4
level" [
 156].
Installer reference guide
249