Connecting the
Arc Monitor
Warning!
Make sure that supply voltage has been switched off!
First connect the trip signal relays and trip contacts. Follow the steps below:
1. Connect wires for Internal Relay Fault, IRF, trip signal relays (K2, K3) and trip
contacts (K4, K5, K6).
2. Use a torque of 0.5 NM
3. Use a screwdriver 2.5 x 0.6 mm (0.98 x 0.23 inches)
4. Cabel area 0.2 - 2.5 mm² (0.078 x 0.98 inches²)
2,5x0,6
0,5 Nm
.
7
2
0,2 ... 2,5 mm
14 12 11
24 22 21
34 32 31
2
0,2 ... 2,5 mm
Installation
43 44
53 54
63 64
37