ABB Arc Guard System TVOC-2 Installation And Maintenance Manual page 76

Hide thumbs Also See for Arc Guard System TVOC-2:
Table of Contents

Advertisement

Technical data
Optical inputs and outputs
Optical detectors
Current signal from CSU
Forward current signal to another Arc Monitor
Trip contacts (K4, K5, K6)
Solid state contacts
Rated voltage 250 V AC/DC
Make and carry for 0.2 s
Make and carry for 1 s 0.15% duty ration
Breaking capacity
Signal relay (K2, K3)
Manual or auto resetable
Rated voltage
Continous carry I
th
Make and carry for 0,2 s
Make and carry for 3 s 10% duty ratio
Breaking capacity
Internal Relay Fault (IRF, K1)
Self supervision alarm relay
Rated voltage
Continious carry I
th
Make and carry for 3 s
Breaking capacity
74
10 inputs (without extensions)
2 inputs X21, X22 (optical)
1 output: X1.23 (optical)
3 NO solid state type IGBT
250 V AC/DC
30 A
10 A
250 V
1.5 A
250 V
1 A
110 V
3 A
48 V
3A
Reinforced insulation between separate contacts.
Voltage drop 5 V 30 A, 3 V 3 A, 2 V 10 mA
Off state current < 1 mA at 250 V
Min. recommended load current 10 mA
2 CO gold-plated contacts
250 V AC/DC
5 A
30 A
15 A
250 V
3 A
250 V
0,3 A
110 V
0,6 A
48 V
2 A
Reinforced insulation between separate contacts
I
= 5 A
th
Min switching load:
1 mA at 5 V DC with contacts not used for switching current
> 0.5 A if inductive/capacitive load before.
1 CO gold-plated contact
250 V AC/DC
5 A
8 A
250 V
1,5 A
250 V
0,15 A
110 V
0,3 A
48 V
0,5 A
Reinforced insulation between separate contacts.
I
= 5 A
th
Min switching load:
1 mA at 5 V DC with contacts not used for switching current
> 0.5 A if inductive/capacitive load before.
AC - 15
DC - 13
DC - 13
DC - 13
AC - 15
DC - 13
DC - 13
DC - 13
AC - 15
DC - 13
DC - 13
DC - 13