Advertisement
A maximum of 130V DC is present across E and C or E and P terminals during measurement or when "SIMPLIFIED MEAS." Button is pressed. Also, it is present across P and C terminals when "BATT. CHECK" button is pressed. Therefore, never touch these terminals with hand. Always, press "BATT. CHECK" button after use so that all the range and function switch buttons are in off (up) position. Then, release "BATT.CHECK" button.
Check to see if the meter pointer is adjusted exactly to the mechanical zero position of the Ω or V scale. If the pointer is off the zero position in either left or right direction open the panel and turn the zero adjust screw behind the panel with a screwdriver. The panel can be lifted up to 90 degrees by holding both sides as shown below.
As shown in figure below, stick the earth bars P and C deep into the earth.
They should be aligned at an interval of 5m to 10m from the earthed equipment e. Connect the green lead wire to the terminal E of the instrument, yellow wire to terminal P and red wire to terminal C. Make sure to stick the auxiliary earth bars in the moist part of the earth. Give enough water where the auxiliary earth bars have to be stuck into the dry, stony or sandy part of the earth so that it may become moist.
Where it is not possible to drive the auxiliary earth bars into a hard surface such as concrete ground, lay the earth bars there, covet them with a cloth and put water (preferably salt water).This may allow earth resistance measurements. (However, this is not possible with asphalt ground)
NOTE:
When connecting the lead wires, make sure that they are separated. If the measurement is made with the lead wires twisted or in touch with each other it will be affected by the induction of current or voltage.
When the resistance of auxiliary earth bars exceeds 2KΩ it may result in measurement errors. Therefore, be careful in sticking the auxiliary earth bars P1 and C1 into the moist earth. Also, ensure sufficient connections between the respective terminals and lead wires.
Press the AC V button and check earth voltage. Earth voltage will be indicated on the V scale. When earth voltage is more than 5V it may result in errors in earth resistance measurement. To avoid this make earth resistance measurement after turning off the power source of the equipment under test or reducing earth voltage.
Note:
Even when either of range switch buttons x1Ω, x10Ω and x100Ω is pressed it does not affect earth voltage measurement.
With "BATT.CHECK" button pressed, the following can be checked simultaneously:
Battery voltage
Battery voltage is sufficient when the meter pointer stays in GOOD area of the battery check scale. If not, replace with the new batteries in accordance with instructions.
Lead wire connection
"OK" lamp lights up when lead wire connection to P and C terminals is good and earth resistance of auxiliary earth is within a limit of tolerance. If it does not illuminate, check for lead wire connection to P and C terminals or lower auxiliary earth resistance to a proper level by changing earth bar location or making the ground moist with water.
Red and yellow lead wires can be checked for possible breakage by shorting the alligator clips at the end of each wire.
NOTE:
There is no need for lead wire connection when battery voltage only is checked. Simply push "BATT.CHECK" button. "OK" lamp will not illuminate.
Press either of x1Ω,x10Ω and x100Ω range switch buttons. Then press the "MEAS." Button. Multiply the reading by 10 at x10Ω or 100 at x100Ω.
"OK" lamp is on when the instrument is in normal operation. If not, it indicates an excessive earth resistance across C and E terminals that does not permit a normal operation. Recheck for possible contact between each lead wire and earth resistance of auxiliary earth bars in accordance with the instructions. In case "OK" lamp does not illuminate and the meter pointer deflects up full scale despite all preceding checks, possible causes are considered an abnormal condition existing in earthed equipment under test, breakage of connection wires from that equipment or breakage of the green lead wire.
4-5-1 This method is recommended where an earth resistance higher than 10 ohms is measured or where it is not possible to drive auxiliary earth bars. An approximate value of earth resistance can be obtained by the two wire system which utilizes existing earthed equipment as shown in Fig.4.
4-5-2 Measurement methods are illustrated in Fig.4.
NOTE:
When making earth resistance measurements using commercial power supply(A),make sure that earth side is connected to P terminal.
4-5-3 Press "AC V" button as outlined in section above for earth voltage measurement of equipment under test and make certain that earth voltage is below 2V. 4-5-4 First press "x10Ω" button and "MEAS." button next Then read earth resistance. When the meter pointer deflects up full scale, press "x100Ω" button. The reading obtained (RE) is and approximate earth resistance value. There is no need for external shorting as P and C terminals are internally shorted. Since measuring current is as low as 2mA, the earth leakage breaker (ELCB) does not trip even if the earth side of the commercial power supply with an ELCB is used.
"OK" lamp is illuminated when the instrument is in normal operation, whether the simplified measurement or normal measurement method is employed.
4-5-5 When the instrument is in working condition, "OK" lamp is illuminated whether the simplified or ordinary measurement is made (This indicates continuity between P plus C terminals and E terminal).However, lead wire connection to P plus C terminals and E terminal). However, lead wire connection to P and C terminals cannot be checked even when "BATT. CHECK" is pressed as the lead wire is not connected to C terminal.
4-5-6 In case of the simplified measurement method where the two terminals only are used, earth resistance "re" of an earthed electrode connecting to P terminal will necessarily be added to a true earth resistance value "REX". Therefore, the earth resistance reading is given as:
RE=REX+re.
If "re" is a known value as follows:
Supposing that RE is 100Ω and an earth resistance to be measured is 100Ω,for example, the true earth resistance value may be expressed as:
REX=(100Ω)-re.
Since re is greater than 0(zero),a true earth resistance may be give as:
REX≤100Ω
In case we measure earth resistance not greater than several tens of ohms we may consider the earth resistance reading obtained as a true value.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the Analog Earth Resistance Tester and is the answer not in the manual?
Questions and answers