Cisco Nexus 9364D-GX2A Hardware Installation Manual
Cisco Nexus 9364D-GX2A Hardware Installation Manual

Cisco Nexus 9364D-GX2A Hardware Installation Manual

Aci-mode switch
Table of Contents

Advertisement

Quick Links

Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation
Guide
First Published: 2022-06-24
Last Modified: 2023-06-23
Americas Headquarters
Cisco Systems, Inc.
170 West Tasman Drive
San Jose, CA 95134-1706
USA
http://www.cisco.com
Tel: 408 526-4000
800 553-NETS (6387)
Fax: 408 527-0883

Advertisement

Table of Contents
loading

Summary of Contents for Cisco Nexus 9364D-GX2A

  • Page 1 Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide First Published: 2022-06-24 Last Modified: 2023-06-23 Americas Headquarters Cisco Systems, Inc. 170 West Tasman Drive San Jose, CA 95134-1706 http://www.cisco.com Tel: 408 526-4000 800 553-NETS (6387) Fax: 408 527-0883...
  • Page 2 Any products and features described herein as in development or available at a future date remain in varying stages of development and will be offered on a when-and if-available basis. Any such product or feature roadmaps are subject to change at the sole discretion of Cisco and Cisco will have no liability for delay in the delivery or failure to deliver any products or feature roadmap items that may be set forth in this document.
  • Page 3: Table Of Contents

    Unpacking and Inspecting a New Switch Planning How to Position the Chassis in the Rack Installing the Chassis in a Four-Post Rack Installing the Switch using the NXK-ACC-KIT2-2RU Rack-Mount Kit Grounding the Chassis Starting the Switch Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 4 System Specifications Environmental Specifications Switch Dimensions Switch and Module Weights and Quantities Transceiver and Cable Specifications Switch Power Input Requirements Power Specifications 3200-W AC/HVDC Power Supply Specifications 3200-W DC/HVDC Power Supply Specifications Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 5 A P P E N D I X C LEDs Switch Chassis LEDs Fan Module LEDs Power Supply LEDs A P P E N D I X D Additional Kits Rack Mount Kit NXK-ACC-KIT2-2RU Accessory Kit NXA-ACC-QDD-DC Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 6 Contents Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 7: Overview

    Overview • Overview, on page 1 Overview The Cisco Nexus 9364D-GX2A switch (N9K-C9364D-GX2A) is a 2-rack unit (RU), fixed-port switch designed for spine-leaf-APIC deployment in data centers. This switch includes the following ports: • 400-Gigabit QSFP-DD ports (64) • 10-Gigabit SFP+ ports (2) •...
  • Page 8 • 3200-W port-side intake DC/HVDC power supply with burgundy coloring (NXA-PDC-3200W-PI) Note Both power supplies are the same type. Do not mix AC, and DC, power supplies. The following figure shows the switch features on the port side of the chassis. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 9 Power supply modules (1 or 2) (AC power supplies shown) numbered from 1 (left) to 4 (right) with slots numbered 1 (top) and 2 (bottom) The following figure shows the side of the chassis. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 10 The switch has port-side intake airflow (burgundy coloring for fan modules), so you must locate the ports in the cold aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut down. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 11: Preparing The Site

    Altitude Requirements Altitude rating is based on power supply installed; see critical components list in the system CB report for altitude rating. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 12: Dust And Particulate Requirements

    The wiring is unlikely to emit radio interference if you use a twisted-pair cable with a good distribution of grounding conductors. If you exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal when applicable. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 13: Shock And Vibration Requirements

    Planning for Power Requirements The switch includes two power supplies (1-to-1 redundancy with current sharing) in one of the following combinations: • Two 3200-W AC/HVDC power supplies • Two 3200-W DC/HVDC power supplies Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 14: Airflow Requirements

    The switch is positioned with its ports in either the front or the rear of the rack depending on your cabling and maintenance requirements. You must have fan and power supply modules that move the coolant air from the cold aisle to the hot aisle in one of the following ways: Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 15: Rack And Cabinet Requirements

    Statement 1048 Rack Stabilization The rack stabilizing mechanism must be in place, or the rack must be bolted to the floor before installation or servicing. Failure to stabilize the rack can cause bodily injury. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 16: Clearance Requirements

    19.0 in (43.3 cm) Note Both the front and rear of the chassis must be open to both aisles for airflow. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 17: Installing The Chassis

    You can install the switch using the following rack-mount options: • Rack-mount kit (NXK-ACC-KIT2-2RU) which you can order from Cisco. For four post racks. • Rack-mount kit (N9K-C9300-RMK) which you can order from Cisco.
  • Page 18: Unpacking And Inspecting A New Switch

    The shipment should include the following: • Switch chassis, which includes the following installed components: • Two power supplies (any combination of the following with the airflow direction being the same as for the fan modules): Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 19: Planning How To Position The Chassis In The Rack

    Installing the Chassis in a Four-Post Rack Before you install the chassis, be sure that the rack is fully secured to the data center floor. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 20: Installing The Switch Using The Nxk-Acc-Kit2-2Ru Rack-Mount Kit

    Install the two inner rails to the sides of the chassis using flat-head screws, as shown in the following illustration: Step 2 Install the two outer rails to the front posts of the rack by aligning the rails to the post holes, as shown in the following illustration: Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 21 Installing the Switch using the NXK-ACC-KIT2-2RU Rack-Mount Kit Step 3 Fasten the two outer rails to the front posts of the rack by pushing the latch into place, as shown in the following illustration: Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 22 Installing the Switch using the NXK-ACC-KIT2-2RU Rack-Mount Kit Step 4 Install the two outer rails to the back posts of the rack by extending them into place, as shown in the following illustration: Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 23 Installing the Switch using the NXK-ACC-KIT2-2RU Rack-Mount Kit Step 5 Fasten the two outer rails to the back posts of the rack by pushing the latch into place, as shown in the following illustration: Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 24 Then secure the retainer screws on the inner rails into the rack, as shown in the following illustration: Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 25 Then slide the retainer screws out to align with the rack and then secure the thumb-screws on the inner rails into the rack, as shown in the following illustration: Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 26: Grounding The Chassis

    Any paint or other non-conductive coatings shall be removed on the surfaces between the mounting hardware and the enclosure or rack. The surfaces shall be cleaned and an antioxidant applied before installation. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 27 Secure the grounding lug to the chassis grounding pad with two M4 screws, see the previous figure. Tighten the screws to 11 to 15 in-lb (1.24 to 1.69 N·m) of torque. Step 4 Prepare the other end of the grounding wire and connect it to the facility ground. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 28: Starting The Switch

    • When connecting to an HVDC power source, do the following: 1. Verify that the power is turned off at a circuit breaker for the power source terminals. 2. Remove the nuts from each of the terminal posts for the power supply. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 29 A setup utility automatically launches the first time that you access the switch and guides you through the basic configuration. For instructions on how to configure the switch and check module connectivity, see the appropriate Cisco Nexus 9000 Series configuration guide.
  • Page 30 Installing the Chassis Starting the Switch Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 31: Connecting The Switch To The Aci Fabric

    As shown in the following figure, each APIC is connected to one or two leaf switches and each leaf switch should be connected to every spine switch in the same fabric. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 32: Preparing To Connect To Other Devices

    Cisco equipment. In situations where long parallel cable runs cannot be separated by at least 3.3 feet (1 meter), we recommend that you shield any potential noise sources by housing them in a grounded metallic conduit.
  • Page 33: Connecting Leaf Switches To Apics

    Connecting Leaf Switches to APICs You must downlink one or two (recommended for redundancy) Cisco Nexus 9300 platform ACI-mode leaf switches to each Application Policy Infrastructure Controller (APIC) in your ACI fabric. The type of virtual interface card (VIC) installed on the APIC determines the types of interface cables that you can use to connect the leaf switches to the APICs.
  • Page 34 Connect the other end of the interface cable to a downlink port on a leaf switch. • For a Cisco 10GBASE-LR or -SR transceiver and cable, insert the transceiver into a downlink optical port on a leaf switch before connecting the cable to the transceiver.
  • Page 35: Connecting Leaf Switches To Spine Switches

    You cannot include NX-OS line cards in the same chassis when running in ACI mode. Note Multiple uplinks from a leaf switch to a spine switch is supported. A symmetrical topology is recommended so that all devices have equal access to resources. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 36: Installing A Gigabit Ethernet Module (Gem)

    Migration of Nodes From a First Generation Switch to a Second Generation Switch You have first generation Cisco Nexus 9000 series switches that may or may not be comprising a virtual port channel (vPC). You are migrating to second generation Cisco Nexus 9000 series switches using the same cables.
  • Page 37 Before you begin • Move any Cisco Application Policy Infrastructure Controllers (APICs) that are connected to the first generation switches that you are migrating to any other switches in the fabric and wait for the Cisco APIC cluster to become "Fully Fit."...
  • Page 38: Setting Up An Optional Console Interface

    Register the new second generation switch with the Cisco APIC. Register the new node with the same node name and node ID. This switch becomes part of the fabric. The Cisco APIC pushes the policies to the new switch and keeps down the vPC legs because there is a mismatch of the generation of switches.
  • Page 39: Setting Up An Optional Management Connection

    DB-9 connector on the other end of the cable to the serial port on the console device. What to do next You can now perform the initial configuration for the switch (see the Cisco ACI Getting Started Guide). Setting Up an Optional Management Connection You can optionally set up an out-of-band management connection for monitoring and troubleshooting purposes.
  • Page 40 • Inspect routinely for dust and damage. If you suspect damage, clean and then inspect fiber ends under a microscope to determine if damage has occurred. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 41: Replacing Components

    Hold the module by its handle and do not touch the electrical connectors on its backside. Also, to protect the electrical connectors, avoid letting them come in contact with anything other than the electrical connectors inside the chassis. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 42: Replacing A Power Supply Module

    If the STS LED does not turn on, slide the module out of the chassis, and visually check the electrical connectors on the back side of the chassis for damage. If damaged, contact Cisco Technical Assistance for help. If undamaged, repeat the previous step to reinstall the module.
  • Page 43: Installing An Ac Power Supply

    Attach the power cable to the electrical outlet on the front of the power supply. Step 4 Make sure that the other end of the power cable is attached to the appropriate power source for the power supply. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 44 Depending on the outlet receptacle on your power distribution unit, you might need the optional jumper Note cable to connect the switch to your outlet receptacle. Step 5 Verify that the power supply is operational by making sure that the power supply LED is green. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 45: Rack Specifications

    • Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see Requirements Specific to Perforated Cabinets, on page Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 46: Requirements Specific To Standard Open Racks

    • The roof should be perforated with at least a 20 percent open area. • The cabinet floor should be open or perforated to enhance cooling. The Cisco R Series rack conforms to these requirements. Cable Management Guidelines To help with cable management, you might want to allow additional space in the rack above and below the chassis to make it easier to route all of the fiber optic or copper cables through the rack.
  • Page 47: System Specifications

    5 to 90% Altitude Operating 0 to 13,123 feet (0 to 4,000 meters) Switch Dimensions Switch Width Depth Height Cisco Nexus 9364D-GX2A 17.41 inches (44.23 29.82 in (75.76 cm) 3.45 inches (8.76 cm) (2 Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 48: Switch And Module Weights And Quantities

    Maximum Power Heat Dissipa Consumption (AC or Requirement Cisco Nexus 9336D-GX2A 1378 W 3000 W 10,236.426 BTUs per ho Power Specifications Power specifications include the specifications for each type of power supply module. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 49: 3200-W Ac/Hvdc Power Supply Specifications

    90% or greater (20 to 100% load) Redundancy Modes Combined, n+1, and n+n RoHS Compliance Hot Swappable Power Cable Specifications The following sections specify the power cables that you can order and use with this switch. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 50: Power Cables For Nxa-Pac-3200W Power Supplies

    The following table lists the regulatory standards compliance for the switch. Table 1: Regulatory Standards Compliance: Safety and EMC Specification Description Regulatory compliance Products should comply with CE Markings according to directives 2004/108/EC and 2006/95/EC. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 51 • CNS13438 Class A EMC: Immunity • EN55024 • CISPR24 • EN300386 • KN 61000-4 series RoHS The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 52 System Specifications System Specifications Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 53: Switch Chassis Leds

    Amber Port admin state is 'Disabled, or the SFP is absent, or both. Port admin state is 'Enabled' and SFP is present, but interface is not connected. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 54: Fan Module Leds

    • Power supply is installed in the chassis but was disconnected from the power source. Flashing amber Power supply is installed without a connection to a power source. (10 seconds) then amber Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 55 LEDs LEDs OK LED FAIL or FAIL/ID Status Amber Power supply failure—possibly one of the following conditions: • Over voltage • Over current • Over temperature • Power supply fan failure Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 56 LEDs LEDs Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 57: Additional Kits

    Not applicable Hazardous substances list for customers in China The following table lists and illustrates the console cable (CAB-CONSOLE-RJ45) that can be ordered. Illustration Description Quantity Console cable with DB-9F and RJ-45F connectors Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...
  • Page 58: Accessory Kit Nxa-Acc-Qdd-Dc

    The following table lists and illustrates the port dust cover (NXA-ACC-QDD-DC). Illustration Description Quantity The port dust cover is designed to protect the connectors in unused ports and help divert airflow for better thermal dispensation. Cisco Nexus 9364D-GX2A ACI-Mode Switch Hardware Installation Guide...

Table of Contents