A. FAN MOTORS
1. Remove cabinet's left-side panel (when looking at the front of the unit).
2. Evaporator fan motor—disconnect evaporator motor wires from evaporator fan
capacitor and power module. Condenser fan motor—disconnect condenser
motor wires from condenser fan capacitor and power module.
For all model sizes 12, 18, 24, and 36
3.
-ring to blower housings (all screws are external and visible), and remove blower
wheel-motor assembly. Remove the blower wheel set screw and disassemble the
blower wheel from the motor shaft and remove the motor.
For model size 60
securing the motor mount to the blower housing and remove motor and mount.
Remove the motor from the motor mount.
4. Install the new motor, reversing the removal procedure.
B. ELECTRONIC CONTROLLER (THERMOSTAT)
To remove the heat/cool display, remove the cabinet's left-side panel (from front).
Locate the two nuts securing the display to the front panel. Unplug the display
cable and remove display. Install new display and secure. Plug in display cable.
C. POWER MODULE
To remove the power module, remove the rear control box cover. Disconnect wires
(one at a time), and re-attach each wire, while holding replacement module in other
hand. Once all wires have been reconnected in accordance with the wiring diagram,
install new power module.
D. CONDENSATE PUMP (ON ALL 5-TON UNITS, OR ON UNITS WHERE THE
CONDENSATE PUMP KIT HAS BEEN INSTALLED)
1. Remove side panel.
2. Remove brackets securing condensate pump in base pan, or condensate tank tray
pan
3. Disconnect pump wire leads at Molex connectors. Remove retainer clamp and
tubing.
4. Replace pump, install by reversing procedure.
E. HIGH PRESSURE SAFETY SWITCH
1. Remove cabinets right side panel, or right rear side panel of Model 60.
2. Remove flare nut that secures capillary to the refrigeration system high pressure
side. A schrader valve is located in the discharge port which allows removal without
losing the refrigerant charge.
3. Remove two screws that secure high pressure switch.
4. Disconnect wire leads from power module and condensate pump safety switch.
5. Install new High Pressure Switch, and splice in new wire leads with existing
control wires. Then reverse in order to complete the procedure.
To gain access to compressor and compressor run capacitor, remove left hand side
panel.
—TO AVOID INJURY, DISCONNECT UNIT POWER
PRIOR TO SERVICING
—loosen blower wheel shaft set screw, and remove the screws
, remove the screws securing motors and inlet