OCEANAIRE 2OACH Series Engineering, Installation And Service Manual page 20

Portable air-cooled heat pump
Table of Contents

Advertisement

FAN SPEED
—The operator can select between AUTO or MANUAL fan speed
control. Pressing the FAN SPEED button will switch speed from AUTO to MANUAL.
In MANUAL mode, pressing the FAN SPEED button will change fan speed from low
to high. In AUTO mode, the fan speed is controlled automatically. In cooling mode,
the controller automatically adjusts the fan speed to high, and as the inside tempera-
ture approaches the set point, the fan speed will reduce. In heat mode, the fan speed
adjusts from low to high as the temperature reaches the set point
TEMP SELECT
INSIDE = return air temperature, DISCHARGE = supply air temperature,
SET POINT can be seen and adjusted by pressing ▲ or▼.
1) Make sure the unit has
2) Press the power button "OFF".
3) Press the following buttons in sequence
S
(
elect—
4) The display will begin flashing P1 and a number.
5) To adjust any program feature, press the ARROW UP▲ or ARROW DOWN ▼ button
until the desired value is displayed.
6) Use the "MODE" button to scroll through the programmable settings P1 through P16.
7) If no buttons are pressed, the display will then return to the "OFF" position after
about 50 seconds.
P1—High Fan Speed Limit Setting. 56 - 85
P2—Low Fan Speed Limit Setting, 30 - 55
P4—Temperature Sensor Calibration, +/- 10°
P10— Temperature Display, °F or °C
P13—Supply Fan Operation, Cycling or Continuous
P1, P2 - To adjust fan speed settings, P1 represents the high fan speed parameter, while
P2 represents the low fan speed parameter. When using nozzle kits, discharge duct
adapters and evaporator plenums, setting P1 to 85 will help to avoid freeze ups.
P4 - Adjust the P4 setting to match the actual INSIDE room temperature, if needed.
P10 - Use this parameter to display temperatures in the desired units.
P13 - To cycle the evaporator fan with the compressor, access code P-13. Press the up or
down button to switch to "CYC", which means cycle the fan with the compressor. The
factory default setting is "CON", which means continuous fan operation.
8) Press POWER—you should see an alphanumeric code.
Press POWER and the unit will start at the new settings.
—Allows the operator to view the controller temperatures
CONTROLLER PROGRAMMING MENU
power.
U
D
p arrow —
own arrow —
If there is no display, repeat the sequence,
making sure the unit has power, but is turned OFF.
PROGRAM SETTINGS
"S-U-D-S"
S
elect)
18