5 Electrical installation
A
A
B
C
B
C
A4P
a
Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
5.3.9
To connect the power consumption digital
inputs
Wires: 2 (per input signal)×0.75 mm²
Power limitation digital inputs: 12 V DC / 12 mA detection
(voltage supplied by PCB)
[9.9] Power consumption control.
1 Open the following (see
"3.2.1 To open the indoor
1 Front panel
2 Switch box cover
3 Switch box
2 Connect the power consumption digital inputs cable to the
appropriate terminals as shown in the illustration below.
Installation manual
16
X1 X2
L
N
A4P
a
unit" [ 4  5]):
3
2
1
A
A
B
C
B
C
a
Installation of EKRP1AHTA is required.
3 Fix the cable with cable ties to the cable tie mountings.
5.3.10
To connect the safety thermostat
(normally closed contact)
Wires: 2×0.75 mm²
Maximum length: 50 m
Safety thermostat contact: 16 V DC detection (voltage
supplied by PCB). The voltage-free contact shall ensure the
minimum applicable load of 15 V DC, 10 mA.
[9.8.1]=3 (Benefit kWh power supply = Safety
thermostat)
1 Open the following (see
"3.2.1 To open the indoor
1 Front panel
2 Switch box cover
3 Switch box
2 Connect the safety thermostat (normally closed) cable to the
appropriate terminals as shown in the illustration below.
1 2
3
4 5
A8P
X801M
1
3 2
5 4
unit" [ 4  5]):
3
2
1
ETBH/X16DF6V+9W
Daikin Altherma 3 H HT W
4P586453-1C – 2020.10