Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
5.3.7
To connect the space cooling/heating ON/
OFF output
INFORMATION
Cooling is only applicable in case of:
▪ Reversible models
▪ Heating only models + conversion kit (EKHBCONV)
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
1 Open the following (see
"3.2.1 To open the indoor
1 Front panel
2 Switch box cover
3 Switch box
2 Connect the space cooling/heating ON/OFF output cable to the
appropriate terminals as shown in the illustration below.
ETBH/X16DF6V+9W
Daikin Altherma 3 H HT W
4P586453-1C – 2020.10
Y1
7
7
9
X2M
A4P
X1M
YC
Y1
a
unit" [ 4  5]):
3
2
1
1+2
2
1
X2M
7
9
A4P Installation of EKRP1HBAA is
3
A4P
Y2
YC
A
A
B
C
B
C
X2M
A4P
a
Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
5.3.8
To connect the changeover to external
heat source
Wires: 2×0.75 mm²
Maximum load: 0.3 A, 250 V AC
Minimum load: 20 mA, 5 V DC
[9.C] Bivalent
1 Open the following (see
"3.2.1 To open the indoor
1 Front panel
2 Switch box cover
3 Switch box
2 Connect the changeover to external heat source cable to the
appropriate terminals as shown in the illustration below.
5 Electrical installation
Wires connected to the space
cooling/heating ON/OFF
output
3
Wire between X2M and A4P
required.
Y2
7
7
9
X2M
A4P
X1M
YC
Y2
a
unit" [ 4  5]):
3
2
1
Installation manual
15