Outdoor Unit Installation Drawings - Daikin RXS71E3V1B Installation Manual

Table of Contents

Advertisement

Outdoor Unit Installation Drawings

Model
Max. allowable length
Min. allowable length
**
Max. allowable height
Additional refrigerant
*
required for refrigerant
pipe exceeding 10m
in length.
Be sure to add the proper amount of additional refrigerant.
*
Failure to do so may result in reduced performance.
The suggested shortest pipe length is 1.5 m, in order to avoid
**
noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how
the unit is installed and the environment in which it is used.)
When connecting the FVXS indoor unit, the shortest piping
length should be no less than around 2.5m.
In sites with poor drainage,
use block bases for outdoor
unit.
Adjust foot height until the
unit is leveled. Otherwise,
water leakage or pooling of
water may occur.
3
50 class
60 class
30m
1.5m
20m
20g/m
Gas pipe
O.D. 12.7mm
Liquid pipe
O.D. 6.4mm
71 class
O.D. 15.9mm
Service lid
Where there is a danger of
the unit falling, use foot bolts,
or wires.
Wrap the insulation
pipe with the finishing
tape from bottom to top.
CAUTION
**Set the piping length
from 1.5m to 30m.
Stop valve cover
Allow space for piping
and electrical servicing.
■English