Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from liquid stop valve and gas stop
valve.
2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a
hexagonal wrench.
4) After two to three minutes, close the gas stop valve and stop
forced cooling operation.
Forced cooling operation
1) Press the Forced Operation switch (SW1) to begin forced cooling. Press the Forced Operation switch (SW1) again to stop forced cooling.
Facility Setting Switch
(cooling at low outdoor temperature)
This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in
a residence or office (the space where there is a human).
1) You can expand the operation range to -15°C by turning on switch B (SW4) on the PCB. If the outdoor temperature falls
to -20°C or lower, the operation will stop. If the outdoor temperature rises, the operation will start again.
CAUTION
1) If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
2) Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
3) Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
4) Use the indoor unit at the highest level of air flow rate.
■English
S102
S2
LED-A
SW4
Forced
operation
switch
SW1
S102
S2
LED-A
Turn on
switch B.
SW4
SW1
Liquid stop valve
Gas stop valve
Service port
(RKS50/60/71E3V1B, RKS50/60F2V1B only)
Hexagonal wrench
Close
Valve cap