Installation Procedure

Step 1 Checking and preparing
accessories
The following accessories are supplied with the indoor
unit. The type and quantity may differ, depending on the
specifications.
Insulation pipe
Cable-tie
Installation manual
Clamp
Installation template
Dimension gauge

Step 2 Choosing the installation location

Installation location requirements
There must be no obstacles near the air inlet and outlet.
Install the indoor unit on a ceiling that can support its weight.
Maintain sufficient clearance around the indoor unit.
Before installing the indoor unit, be sure to check whether the
chosen location is well-drained.
The indoor unit must be installed such that it is beyond public
access and is not touchable by users.
Rigid wall without vibration.
Where it is not exposed to direct sunshine.
Where the air filter can be removed and cleaned easily.
The place where animals may urinate on the product
Ammonia may be generated.
WARNING
Because your air conditioner contains R-32
refrigerant, make sure that it is installed, operated,
and stored it in a room whose floor area is larger
than the minimum required floor area specified in the
following table:
Drain hose
User manual
– m : Total refrigerant charge in the system
– A : Minimum required floor area
IMPORTANT: it's mandatory to consider either the
table above or taking into consideration the local law
regarding the minimum living space of the premises.
Minimum installation height of indoor unit is 0.6 m
for floor mounted, 1.8 m for wall, 2.2 m for ceiling.
CAUTION
As a rule, the unit cannot be installed at a height of
less that 2.5m.
If you install the cassette or duct type indoor unit on
the ceiling with humidity over 80%, you must apply
extra 10mm of polyethylene foam or other insulation
with similar material on the body of the indoor unit.
m (kg)
Ceiling-mounted type (A, m2)
≤ 1.842
No requirement
1.843
1.9
2.0
2.2
2.4
2.6
2.8
3.0
3.2
3.4
3.6
3.8
4.0
4.2
4.4
4.6
4.8
5.0
5.2
3.64
3.75
3.95
4.34
4.74
5.13
5.53
5.92
6.48
7.32
8.20
9.14
10.1
11.2
12.3
13.4
14.6
15.8
17.1