Dryer Alarm Table - Gardner Denver RSD Series Instruction Manual

Refrigerated type compressed air dryers
Table of Contents

Advertisement

Dryer Alarm Table

Alarm Conditions
Alarm Text
Alarm Trigger
DISCHARGE
Discharge temperature >
HIGH TEMPERATURE
high discharge temperature set point
HIGH PRESSURE
High pressure switch open
LOW PRESSURE
Low pressure switch open
COMPRESSOR 1
Motor protection #1 switch open
COMPRESSOR 2
Motor protection #2 switch open
OIL PROTECTION 1
Oil protection #1 switch open
OIL PROTECTION 2
Oil protection #2 switch open
Phase Detection Enabled AND isPhaseReversed()
PHASE REVERSAL
Phase Detection Enabled and isPhaseLoss()
PHASE LOSS
EVAPORATOR
Evaporator temperature > High evaporator temperature
HIGH TEMPERATURE
set point
HEATER 1
Heater #1 switch open
HEATER 2
Heater #2 switch open
DRAIN 1
Drain #1 switch open
DRAIN 2
Drain #2 switch open
SERVICE
Dryer service interval > 0
DRYER
AND Dryer service timer > Dryer service interval
EVAPORATOR
Evaporator temperature sensor out of range
TEMP SENSOR
EVAPORATOR OUT.
Evaporator outlet temperature sensor out of range
TEMP SENSOR
AND evaporator outlet temperature sensor installed
DISCHARGE
Discharge temperature sensor out of range
TEMP SENSOR
SUPERHEAT ALARM
(Evaporator outlet temperature – Evaporator inlet temperature )
> Super heat alarm set point
AND evaporator outlet temperature sensor installed
Delay
Monitored
Exit Condition
1 Second
Always
Alarm reset button pressed
1 Second
Always
Alarm reset button pressed
3 Minutes
Always
Alarm reset button pressed
1 Second
Primary
Alarm reset button pressed
Compressor On
1 Second
Auxiliary
Alarm reset button pressed
Compressor On
1 Second
Always
Alarm reset button pressed
1 Second
Always
Alarm reset button pressed
1 Second
Standby
Alarm reset button pressed
1 Second
Standby
Alarm reset button pressed
1 Second
Dryer On
Alarm reset button pressed
> 10 minutes
1 Second
Standby
Alarm reset button pressed
1 Second
Standby
Alarm reset button pressed
1 Second
Dryer On
Alarm reset button pressed
1 Second
Dryer On
Alarm reset button pressed
None
Always
Alarm reset button pressed
1 Second
Always
Alarm reset button pressed
1 Second
Always
Alarm reset button pressed
1 Second
Always
Alarm reset button pressed
7 Minutes
Dryer On
Alarm reset button pressed
Alarm Action
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
De-energize alarm relay #2
De-energize alarm relay #2
De-energize alarm relay #2
De-energize alarm relay #2
De-energize alarm relay #2
De-energize alarm relay #2
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
Halt compressors
De-energize alarm relay #1
21

Advertisement

Table of Contents
loading

Table of Contents