DRYER ALARM TABLE

Alarm Conditions
Alarm Text
Alarm Trigger
HIGH PRESSURE
High pressure switch open
LOW PRESSURE
Low pressure switch open
COMPRESSOR
Motor protection #1 switch open
HEATER
Heater switch open
DRAIN 1
Drain #1 switch open
DRAIN 2
Drain #2 switch open
SERVICE
Dryer service interval > 0
DRYER
AND Dryer service timer > Dryer service interval
EVAPORATOR
Evaporator temperature sensor out of range
TEMP SENSOR
Delay
Monitored
1 Second
Always
3 Minutes
Always
1 Second
Primary
Compressor On
1 Second
Standby
1 Second
Dryer On
1 Second
Dryer On
None
Always
1 Second
Always
Exit Condition
Alarm Action
Manually reset the
Halt compressors
high pressure switch.
De-energize alarm
Alarm reset button
relay #1
pressed
Alarm reset button
Halt compressors
pressed
De-energize alarm
relay #1
Alarm reset button
Halt compressors
pressed
De-energize alarm
relay #1
Alarm reset button
De-energize alarm
pressed
relay #2
Alarm reset button
De-energize alarm
pressed
relay #2
Alarm reset button
De-energize alarm
pressed
relay #2
Alarm reset button
De-energize alarm
pressed
relay #2
Alarm reset button
Halt compressors
pressed
De-energize alarm
relay #1
25