DANIEL 700 User Manual page 19

Nps 2 through 16 / class 150-600
Hide thumbs Also See for 700:
Table of Contents

Advertisement

User manual
P/N 3-9008-553
Table 2-1: Operating conditions for the control valve
Condition type
Valve capacity
2.1.1
Design considerations
Some conditions to consider:
Service operating pressure
Service testing pressures
Service process temperature and ambient site temperatures
Chemical composition and toxicity of fluid in operating conditions
Traffic, wind and earthquake at loading site
Adverse force or stress caused by inadequate supports, attachments, piping, etc.
Corrosion, erosion, fatigue, etc.
Decomposition of unstable fluids in operating and test conditions
Possible damage from external fire
Mass fluid in process and test conditions
WARNING
FUNCTIONAL AND ENVIRONMENTAL HAZARD
Evaluate the functional and environmental conditions prior to installing a control valve.
Install the control valve in a well-designed piping system.
Failure to comply may result in death or serious injury from pipe failure.
User manual
Operating conditions and specifications
(continued)
Description
C
is a capacity coefficient that defines as the number of US gpm of
v
water that flows through a valve with a pressure drop of 1 psi across
the valve. Daniel valves have the following C
NPS 2: 86 gpm
NPS 3: 186 gpm
NPS 4: 309 gpm
NPS 6: 688 gpm
NPS 8: 1296 gpm
NPS 10: 2040 gpm
NPS 12: 2920 gpm
NPS 16: 5360 gpm
*C
based on wide open valve with water temperature at 60° F (16° C)
v
USER MANUAL
November 2020
:
v
21
19
www.Daniel.com

Advertisement

Table of Contents
loading

Related Products for DANIEL 700

This manual is also suitable for:

V707

Table of Contents