ABB MKey RFID Series Product Manual page 24

Rfid dual interlock safety switch with guard locking
Table of Contents

Advertisement

Safety-related characteristic data and
Conformity
Safety Classification for Guard position and lock monitoring :
These values are correct provided the OSSD outputs are connected to a suitable logic device,
for example, ABB Electrification Sentry safety relays. Both channels must be used.
Characteristic data according to IEC 62061:2021 (used as a subsystem)
Safety Integrity Level
PFH (1/h)
PFD (Av.)
Proof Test Interval T1
Characteristic data according to EN ISO 13849-1:2015
Performance Level
Category
MTTF
D
Diagnostic Coverage DC
Certifications
Information regarding UL Standards: Type 1 enclosure. Use Class 2 power supply or equivalent.
Maximum temperature 40°C.
Use 16-28AWG copper conductors (rated 90°C). Terminal Torque 6 lb ins. (0.7 Nm).
Intended for same polarity use. Safety Circuits (11-12 & 21-22) 24 V DC 200 mA max.
Use one polymeric conduit connection. Not suitable for connection to rigid metal conduit.
Earth bonding terminal inside metal enclosures (if required). Use 16-12AWG conductors.
2TLC010088M0201
Rev.A
SIL 3
1.0 E-09 (Corresponds to 1% of SIL3)
8.7 E-05 (Corresponds to 9% of SIL3)
20 a
e
Cat 4.
771 a
High
TÜV, cULus
24