15. Power Saving Details Setting
Step7. Change level
Press " " or " " to select the item to set and press "OK".
It changes in the order of "Low <-> Med <-> High" ↔ "Low
only" ↔ "Med only" ↔ "High only".
Press " " to return to Step 3.
NOTES:
For the sub remote controller, only the level switching order can be set.
If the "Power Savings Mode" changes the "Power Saving Details Setting" in outdoor capacity control, the
"Power Savings ON/OFF" turns OFF.
The outdoor capacity can be clarified as "Low Power Savings " > "Med Power Savings" > "High Power Savings".
The cooling/heating capacity can decrease when using the "Power Savings" function.
(2) Indoor Unit Rotation Control Setting
Item
Address Order
Control Method
Temperature Order
Sensor Order
Change Level
1.
Set Indoor Unit Rotation Control
Step1. Select "Service Menu" on the Service & Installation screen
and press "OK".
Step2. Select "Power Saving Details Setting" and press "OK".
→ Power Saving Details Setting screen is displayed.
Step3. Select "Rotation Control" and press "OK".
Step4. Press " " or " " to select the setting item.
The items "Control" and "Fan Mode Time" are displayed in
order.
Step5. Change the Control Method
Select "Control" and press "OK".
Press " " or " " to select the item to set and press "OK".
It changes as follows:
"Address Order" ↔ "Temperature Order" ↔ "Sensor Order".
Press " " to return to Step4.
※Cannot be set if the indoor/outdoor unit does not support
this function.
31
The number (address) assigned by the previous indoor unit changes the FAN mode of the
indoor unit in ascending order.
The difference between the temperature setpoint and the indoor unit intake temperature
changes the FAN mode in ascending order for the indoor unit.
If the motion sensor is used, this function changes the FAN mode in order, from the indoor
unit in a spacious area with few people.
It is possible to change the timing of the FAN operation of the indoor unit.
Intermittent Control
Low <-> Med <-> High
Low only
Med only
High only
Select setting range of power savings.
Select
OK
Description
Power Saving Details Setting
Capacity Control
Rotation Control
Intermittent Control
Reset Default
OK
Select
Rotation Control
Control
Fan Mode Time
: 3 min
Change units to Fan operation in order from the unit with
the smaller address number.
Select
OK
Rotation Control
Address Order
Temperature Order
Sensor Order
Select
OK
Back
Back
Address Order
Back
Back