■Outline drawings
Air exhaust fan
■Attention
1. Do not install the product at regions or locations that exceed the following operating conditions.
( If these operating conditions are exceeded, dew condensation water might drip.)
・Outdoor air temperature is -15 to 40 ℃.
・Surrounding air condition is 0 to 40 ℃ 80%RH, or less
・Absolute humidity of
under the above minimum outdoor air temperature conditions.
2. Do not install Lossnay unit vertically or on an incline.
3. Do not install the Lossnay unit upside down.
4. Provide an inspection opening at least 745 × 530 mm in size. (Locate the inspection opening at a position that allows
the Lossnay unit to be carried to its installation site to perform installation work and that allows the worker to go to the
installation site to perform maintenace.)
5. When connecting the RA (return air) to a bathroom, be sure to branch into two lines and return air from two locations, the
bathroom and living room.
6. The duct connecting flange of the Lossnay unit can accommodate 100, 125 and 150 mm dia. ducts.
7. For installation work parts, be sure to use only accessories and designated parts.
8. Please note a clear working space is required around the installed product to allow the cover to be removed and provide
sufficient access for maintenance such as filter change.
9. The product must be installed indoors.
OUTLINE DRAWINGS
Surrounding air
or less where the dew point temperature of 12 ℃ (ex.20 ℃ 60%RH) is reached
DATE
5-Nov-2015
Air Supply fan
Lossnay core
※Specification may be subject to change without notice.
TYPE
Heat Recovery Ventilator LOSSNAY
MODEL
VL-220CZGV-E
N15SGGD0004A
NUMBER
Contol box
UNIT
SCALE
mm
N.T.S
2/5