5.7

Blast tube length

The length of the blast tube 9)(Fig. 8) must be selected according
to the indications provided by the manufacturer of the boiler, and
in any case it must be greater than the thickness of the boiler door
complete with its fettling.
The range of lengths available, L (mm), is as follows:
Blast tube 9)(Fig. 8)
RL 70/M
RL 100/M
RL 130/M
5.8

Securing the burner to the boiler

Disassemble the blast tube 9)(Fig. 8) from the burner 6) by pro-
ceeding as follows:
 loosen the four screws 3) and remove the cover 1);
 remove the screws 2) from the two slide bars 5);
 remove the two screws 4) fixing the burner 6) to the flange
7);
 withdraw the blast tube 9) complete with flange 7) and slide
bars 5).
5.9

Combustion head calibration

At this point check, for model RL 130/M, whether the maximum
nd
delivery of the burner in 2
B or in area C of the firing rate. See page 11.
If it is in area B then no operation is required.
If, on the other hand, it is in area C:
– unscrew the screws 1)(Fig. 9) and disassemble the blast tube
5);
– unscrew the screws 3) and remove the shutter 4);
– tighten the screws 3) on the rod 2);
– now refit the blast tube 5) and the screws 1).
Short
Long
272
385
272
385
272
385
stage operation is contained in area
D690
Installation
For boilers with front flue passes 12)(Fig. 8) or flame inversion
chambers, protective fettling in refractory material 10) must be in-
serted between the boiler fettling 11) and the blast tube 9).
This protective fettling must not compromise the extraction of the
blast tube.
For boilers having a water-cooled front the refractory fettling 10)-
11) is not required unless it is expressly requested by the boiler
manufacturer.
D1219
Once this operation has been carried out (if it was required), se-
cure flange 7)(Fig. 8) to the boiler plate interposing the supplied
gasket 8).
Use the 4 screws provided after having protected the thread with
antiscruffing products.
The burner-boiler seal must be airtight.
WARNING
15
GB
Fig. 8
Fig. 9