Goodman ComfortNet ASXC Series Service Instructions Manual page 80

Condensing units, split system heat pumps with r-410a refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

SERVICING
Speed Selection Dip Switches
Cool
Adjust
Selection
Selection
Switches
Switches
TAP
S1
S2
S3
A
OFF
OFF OFF OFF OFF OFF
B
ON
OFF ON
C
OFF
ON
OFF
D
ON
ON
ON
Profiles
Pre-Run
A
-------
B
-------
C
-------
D
30 sec/50%
To set Airflow: (1) Select model and desired High Stage Cooling
Airflow. Determine the corresponding tap (A, B, C, D). Set dip
switches S1 and S2 to the appropriate ON / OFF positions.
(2) Select model and installed electric heater size. Set dip
switches S9, S10, and S11 to the appropriate ON / OFF positions.
(3) If airflow adjustment is required set Trim Enable Switch
ON (OFF = 0% Trim) and set S3 and S4 to appropriate ON / OFF
positions. Tap A is +5%,Tap B is -5%, Tap C is +10%, Tap D is
-10%.
To Set Comfort mode: Select desired Comfort Mode Profile (see
profiles above). Set dip switches S5 and S6 to appropriate ON /
OFF positions.
Dehumidification: To enable, set dip switch S7 to ON. Cooling
airflow will be reduced to 85% of nominal value during cool call
when Dehum command is present. To disable, set S7 to OFF.
Continuous Fan Speed: Use dip switches S12 and S13 to select
one of 4 continuous fan speeds, Tap A is 25%. Tap B is 50%, Tap
C is 75%, Tap D is 100%.
Notes:
1. Airflow data shown applies to legacy mode operation only.
For a fully communicating system, please see the outdoor
unit's installation instructions for cooling and heat pump
airflow data. See ComfortNet System-Airflow Consideration
section for details.
2. Airflow blink codes are approximations of actual airflow.
80
Profile
Continuous
Selection
Fan
Switches
Speed
S4
S5
S6
S12
S13
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
ON
Short-Run
OFF Delay
--------
60 sec/100%
30 sec/50%
60 sec/100%
7.5 min/82%
60 sec/100%
7.5 min/82%
30 sec/50%
S8
Cooling/Heat Pump Airflow Table
Model
AVPTC24B14**
AVPTC30C14**
AVPTC36C14**
AVPTC48C14**
to
AVPTC42D14**
AVPTC48D14**
AVPTC60D14**
NOTE: Airflow blink codes are approximations of actual airflow.
provided are at 0.3 static.
Low stage
Speed tap
(CFM)
410
A
565
B
C
660
765
D
440
A
605
B
C
740
885
D
A
500
B
700
C
930
1120
D
500
A
700
B
C
930
1120
D
A
560
763
B
C
994
1225
D
A
900
1035
B
C
1140
1200
D
A
1210
1365
B
C
1450
1525
D
High stage
(CFM)
610
835
970
1125
610
835
1020
1225
725
1000
1330
1600
725
1000
1330
1600
800
1090
1420
1750
1350
1550
1700
1800
1610
1815
1920
2025
Airflows