Information And General Instructions; Product Disclaimer Statement - Riello RDB4.2 FIREBIRD C58/200K Installation, Use And Maintenance Instructions

Table of Contents

Advertisement

2.3.1

Information and general instructions

To ensure consistency, the supplier of the fuel must be able to
demonstrate compliance with a recognised Quality Control and
management system to ensure high standards are maintained
within the storage, blending and delivery processes.
The installation oil storage tank and its ancillaries must also be
prepared BEFORE liquid Bio fuel is introduced.
Checks and preparation should include:
 For new installations, make sure that all materials and seals
in the oil storage and supply line to the burner are compati-
ble with Bio fuels. For all installations, there must be a good
quality bio compatible oil filter at the tank and then a sec-
ondary filter of 60 Microns protecting the burner from con-
tamination.
 If an existing oil storage tank is to be used then in addition
to the materials checks as detailed above, it will be essen-
tial that the tank is first inspected for condition and checked
for water or other contamination. Riello strongly recom-
mends that the tank is cleaned and oil filters replaced prior
to Bio fuel delivery. If this is not completed then due to the
hydroscopic nature of Bio fuel, it will effectively clean the
tank, absorb water present which in turn will result in equip-
ment failure that is not covered by the manufacturer's war-
ranty.
 Depending on the capacity of the oil storage tank and oil
usage, fuels may remain static within the tank for some con-
siderable time and so Riello recommends that the oil distrib-
utor is consulted regarding the use of additional Biocides
within the fuel to prevent microbial growth from occurring
within the tank. Riello suggests that fuel suppliers and or
service companies are contacted for guidance on fuel filtra-
tion. Special attention should be applied to duel fuel applica-
tions where oil may be stored for long periods of time.
 The burner must be set according to the appliance applica-
tion and commissioned checking that all combustion param-
eters are as recommended in the appliance technical
manual.
 Riello recommends that the in line and burner oil pump fil-
ters are inspected and if required replaced at least every 4
months during burner use, before the burner start-up follow-
ing a long period of discontinue operation and even more
frequently where contamination has occurred. Particular
attention is needed when inspecting and checking for fuel
leakages from seals, gaskets and hoses.
20037625
Information and general warnings
2.3.2
CAREFULLY READ THE FOLLOWING DISCLAIMER. YOU
ACCEPT AND AGREE TO BE BOUND BY THIS DISCLAIMER
BY PURCHASING RIELLO BIO COMPATIBLE BURNERS
AND/OR COMPONENTS.
Although the information and recommendations (hereinafter "In-
formation") in this guidance is presented in good faith, believed to
be correct and has been carefully checked, Riello (and its subsid-
iaries) makes no representations or warranties as to the com-
pleteness or accuracy of the Information. Information is supplied
upon the condition that the persons receiving same will make
their own determination as to its suitability for their purposes prior
to use. In no event will Riello (and its subsidiaries) be responsible
for damages of any nature whatsoever resulting from the use of
or reliance upon Information.
Other than set forth herein, Riello (and its subsidiaries) makes no
additional warranties with respect to the bio compatible burner,
either express or implied, including that of merchantability or fit-
ness for a particular purpose or use.
In no event shall Riello (and its subsidiaries) be liable for any in-
direct, incidental, special or consequential damages including,
without limitation, loss of profits, damages for loss of business
profits, business interruption, loss of business information, loss of
equipment, or other pecuniary loss or compensation for services
whether or not it is advised of the possibility of such damages.
With the exception of injuries to persons, Riello's liability is limited
to the customer's right to return defective/non-conforming prod-
ucts as provided by the relevant product warranty.
6