Electrical Wiring; Control Box - Riello RDB4.2 FIREBIRD C58/200K Installation, Use And Maintenance Instructions

Table of Contents

Advertisement

7.2

Electrical wiring

~
50Hz - 230V
PE
L
N
Main switch
T6 A
Safety
thermostat
Limit
thermostat
4 pole socket
4 pin plug
Burner-earth
Motor
Black
White
Capacitor
 Do not swap neutral and phase over, follow
the diagram shown carefully and carry out a
good earth connection.
 The electrical wiring carried out by the
WARNING
installer must be in compliance with the rules
in force in the country.
 The section of the conductors must be at
least 1mm
local standards and legislation).
TESTING:
Check the shut-down of the burner by opening the thermostats
and the lock-out by darkening the photoresistance.
Electrical system
Remote lock-out signal
(230V - 0.5A max.)
Ignition
electrodes

CONTROL BOX

535SE/LD
D4218
Photoresistance
Oil valve
Blue
2
. (Unless requested otherwise by
7.2.1
Control box
This operation must be performed with the burner
turned off and mains power disconnected.
DANGER
To remove the control box (Fig. 15) from the burner follow of the
istruction:
 Loosen the screw 1), open the protection 2) and remove all
components.
 Remove the coil 3).
 Loosen the two screws 4).
 Move a little the control box and remove the high voltage
leads.
4
3
4
Fig. 14
17
GB
2
1
E9154
Fig. 15
20037625