Setting Data Table - Air Regulation - Ecoflam MAX 15 HT Manual

Light oil burners
Hide thumbs Also See for MAX 15 HT:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 6
EN
Start up

- Setting data table - Air regulation

NOZZLE
gph
spry
1,50
60°
1,65
60°
1,75
60°
2,00
60°
2,25
60°
2,50
60°
2,75
60°
3,00
60°
3,50
60°
4,00
60°
The settings above are basic settings.
These adjustment values are normally
suitable for commissioning the burner.
These values have been determined in
our test labs and are useful for the first
A
A
MIN
14
www.ecoflam-burners.com
PUMP
OUTPUT
bar
kg/h
12
6,2
12
7,0
12
7,6
12
8,3
12
9,3
12
10,4
12
11,5
12
12,5
12
14,9
11
16,0
switch-on as final setting must be done
using a combustion analyzer.
Favourable combustion values can be
achieved using the following nozzles:
B
MAX
FIRING HEAD SETTING
Pos.
0
1
2
2,5
3
3,5
4
4,5
5
5
Air damper setting (A).
Unscrew the fixing screw with the hexago-
nal spanner:
• turn the air damper clockwise, to reduce
output.
• turn the air damper counterclockwise
, to increase output.
Reached the desired value to fix the
screw.
Firing head setting (B).
To act on the screw in figure:
• turn Allen key till you reach the
requested value (index 0-5).
AIR DAMPER SETTING
Pos.
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°
420010372102

Advertisement

Table of Contents
loading

Table of Contents