Download Print this page

Sierra Wireless LX40 Connecting Manual page 4

Connecting lte router to an eaton network card
Hide thumbs Also See for LX40:

Advertisement

INDGW-M2 or INDGW-X2 Card Installation
Figure 4. INDGW-M2 or INDGW-X2 Card Firmware Tab
4.
Note the latest available firmware version. If that version is later than the one on the network card, update
the card firmware:
a.
Click the link to download and save that file to a known location.
b.
Remain connected to the card via the USB cable using the redirected IP address http://169.254.0.1.
c.
Select Maintenance from the left-hand menu and select Firmware at the top to display the UPDATE
FIRMWARE page (see
d.
Click Upload to load the latest firmware to the card. Click Choose File to navigate to the firmware file
saved in Step 4.b.
e.
Select the firmware file and click Upload.
f.
When the firmware update is completed, a prompt is displayed. Allow the card to reboot and wait 2–4
minutes for completion.
g.
Log into the card, return to the Firmware tab, and confirm that the firmware updated was successful.
E E n n v v i i r r o o n n m m e e n n t t a a l l M M o o n n i i t t o o r r i i n n g g P P r r o o b b e e ( ( E E M M P P ) ) G G e e n n 2 2 I I n n s s t t a a l l l l a a t t i i o o n n
1.
Remove the EMP and cable from the packaging.
2.
Install the EMP as directed in the
Environmental Monitoring Probe Gen2 EMPDT1H1C2 Installation
Set the MODBUS ADDRESS switches on each EMP as appropriate for your application (see
For example, for an application with one EMP, set the switches as shown in
and TER (termination) in the 1 position. For a multiple-EMP application, at least one switch must be
set on each EMP in in the daisy-chain and the TER switch set on the last EMP in the daisy-chain.
NOTE
4
Connecting a Sierra Wireless LX40 Router to an Eaton Network Card
Figure
4).
If the double-sided tape provided with the EMP is not used to attach the EMP, it may be
used to secure the Sierra Wireless LX40 LTE router (see
Installing and Connecting the Sierra Wireless LX40 LTE
Instructions.
Router.
P-164001160—Rev 01
Figure
5).
Figure
5, with switch 1

Advertisement

loading