7.2
Electrical wiring
~
50Hz - 230V
L
N
Main switch
T6A
TS
SB
TL
1
5
3
XP6
CONTROL BOX
N L
TB
C
M V
Legend
C
- Capacitor
E
- Ignition electrodes
F
- Photoresistance
MV
- Fan motor
SB
- Remote lock-out signal (230V - 0.5A max.)
TB
- Burner-earth
TL
- Limit thermostat
TS
- Safety thermostat
T6A - Fuse
V
- Oil valve
XP6 - 6 pin plug
Do not swap neutral and phase over, follow
the diagram shown carefully and carry out a
good earth connection.
WARNING
The electrical wiring carried out by the
installer must be in compliance with the rules
in force in the country.
The section of the conductors must be at
least 1mm
local standards and legislation).
20026404
TO BE DONE BY
THE INSTALLER
CARRIED OUT
IN THE FACTORY
535SE/LD
D10390
2
. (Unless requested otherwise by
Electrical system
TESTING:
Check the shut-down of the burner by opening the thermostats
and the lock-out by darkening the photoresistance.
7.2.1
Control box
DANGER
To remove the control box (Fig. 19) from the burner follow of the
istruction:
Loosen the screw 1), open the protection 2) and remove all
components.
Remove the coil 3).
Loosen the two screws 4).
Move a little the control box and remove the high voltage
leads.
4
E
F
3
V
4
Fig. 18
GB
18
This operation must be performed with the burner
turned off and mains power disconnected.
2
E9154
1
Fig. 19