FLOWTECH flowpress Operation And Maintenance Manual

Direct pressurisation unit
Hide thumbs Also See for flowpress:

Advertisement

Quick Links

1
flow
press
©
Direct Pressurisation Unit
OPERATION AND
MAINTENANCE MANUAL
First Publication Date: 01/04/2023
Revision: 1
Revision Date:

Advertisement

Table of Contents
loading

Summary of Contents for FLOWTECH flowpress

  • Page 1 flow press © Direct Pressurisation Unit OPERATION AND MAINTENANCE MANUAL First Publication Date: 01/04/2023 Revision: 1 Revision Date:...
  • Page 2 These instructions are to assist in the installation, Operation and Maintenance of a Flowpress Direct Pressurisation Unit. Please follow them carefully.
  • Page 3 Electrocution, Burns, Fire, Flooding, death or injury to people and/or damage to property dependent upon the circumstances involved. flowtech Water Solutions accepts no responsibility or liability for any damage, losses, injury, fatalities or consequences of any kind due to misapplication, mishandling or misuse of any equipment, or as a result of failure to comply with this manual.
  • Page 4: Warranty

    Flowtech reserve the right to supply a replacement product in lieu of an engineer visit. Removal and reinstallation costs, along with consequential losses are not covered by this warranty agreement.
  • Page 5: About This Manual

    This product is suitable and appropriate for the operation in heat generating systems according to BS7074, BSEN 12828, BSEN 12952 and BSEN 12953. The Principal / Operator, will need to consult with a local authorities on any additional safety measures that are required. flowpress Direct O&M Manual...
  • Page 6: Incoming Goods

    Any attempts to access the internals of the unit without the correct equipment will invalidate the Flowtech Warranty and will be classified as use in an improper manner, according to our Terms and Conditions.
  • Page 7: Other Hazards

    • access to specialist services, advice and manufacturers' data; • effective support and professional expertise within their organisation; and • proper standards of professional integrity. flowpress Direct O&M Manual...
  • Page 8: Product Description

    (e.g. slow leaks, air venting, etc.). The Flowpress Direct is the latest in pumpless digital pressurisation technology for light commercial and residential buildings. It’s a slim, wall-mounted pumpless top-up pressurisation unit, with a top-up flow rate of up to 14 l/min depending on the mains or boosted mains, water pressure.
  • Page 9: Technical Data Sheet

    5°C / 45°C Humidity 60….70% relative humidity, non-considering Keep the unit in a locked, frost free and dry area, protect the unit from solar & thermal radiation, vibration, from electrically conductive gases, explosive gas mixtures and aggressive atmosphere. flowpress Direct O&M Manual...
  • Page 10: Installation Requirements

    Installation Requirements The Flowpress Direct is a wall mounted unit and should be installed at a suitable eye level, where the screen is easy to read and maintenance remains practical and possible. The wall of the set-up location for the Flowpress Direct must be such that stability is guaranteed and maintained.
  • Page 11: Installation Diagram

    Installation Diagram flowpress Direct O&M Manual...
  • Page 12: Clearance Requirements

    Clearance Requirements Clearance guidelines for service and repair Hydraulic Connections From the “Manual-mode” in the controller menu, a testing routine can be triggered to check if the device is set up correctly and working accordingly. Each actuator (valve) can be operated separately with a maximum run-time of 2 minutes.
  • Page 13 RS485 Modbus/Bacnet/HFC over RS485 1 B + 2 B - 3 GND Fuse 1 (P31&P32) 5x20 5A Fuse 2 (P33&P35) 5x20 10AT Fuse 2 (P34&P36) 5x20 10AT Mains power connector 3 PE Mains grommet Not Availible flowpress Direct O&M Manual...
  • Page 14 Identification Description Pinout SELV, System pressure 0-5V 1 + VDC 3 signal 3 GND SELV, Inlet pressure 0-5V 1 + VDC 3 signal 3 GND Not available Not available Not available Not available Not available Not available Not available Not available Not available Not available Fault contact, VFC 1...
  • Page 15: Connectivity Options

    All operations must be carried out by a qualified electrician The Flowtech equipment must be connected to a mains isolator switch with a contact gap of at least 3 m. It is recommended the switch should be installed within 2m of the equipment.
  • Page 16: Alarm Installation

    If controller is powered up, than the is P27 normally closed If controller is in error, than the is P27 normally open. For additional information on how to connect the the Flowpress Direct to the internet or BMS, see the connectivity guide.
  • Page 17: Operation

    A typical venting allowance is 0.3 bar, added to the static height to give the cold fill pressure. The Differential setting represents the allowable pressure loss before the pump activates and restores the cold fill pressure. The Differential setting must not be greater than the system venting allowance. flowpress Direct O&M Manual...
  • Page 18 This will ensure that the system remains fully flooded during normal topup conditions. Once commissioned, the pressurisation unit should operate without any user intervention. Under normal operating conditions, the display will show the current system pressure in Bar. For an overview of the main operation screens, see image below. A clarification of menu icons, function and location can be found in Appendix 1: Icon library Home screen While the unit is filling, the display will show the current status of the unit and its actuators (valves).
  • Page 19: Shutdown Procedure

    Please ensure that when the system cools down or warms up, the minimum or maximum system pressure does not exceed or fall below the permitted operating pressure. Check the Flowpress Direct operation once power supply has been restored and, if necessary, set the actual date and time values (overview menu options).
  • Page 20: Maintenance And Repairs

    Maintenance and Repairs Maintenance and repairs may only be carried out when the system is shut down or if the Flowpress Direct is not required to monitor or operate. The power supply must remain off for the period of the work.
  • Page 21: Visual Inspection

    This water may be chemically treated, contain antifreeze or other additives. Further processing of the construction parts should be carried out in agreement with the required waste management service provider. CONTACT FLOWCARE SERVICE DEPARTMENT ON 0333 200 1813 IF THERE ARE ANY QUERIES OR CONCERNS flowpress Direct O&M Manual...
  • Page 22: Icon Library

    Icon Library...
  • Page 23 Direct O&M Manual...
  • Page 25: Troubleshooting

    The unit is undersized for the Review unit selection exceeded system. Flood limit time is too short. Contact Flowtech Service. Supply The isolation valve at the Open the isolation valves at the pressure bottom of the unit is closed.
  • Page 26 Open the isolation valves at the the unit is closed. bottom of the unit. Maintenance 1 The unit is due an annual service. Contact Flowtech Service. is due Maintenance 2 The unit is due an annual service. Contact Flowtech Service.
  • Page 27 The pressure sensor has failed. Replace pressure sensor signal System The pressure output range is Contact Flowtech Service. pressure out of detectable area. Sensor sensor short needs calibrating. circuit The pressure sensor has failed. Replace pressure sensor...
  • Page 28 Maintenance Maintenance of the pressurisation equipment you have purchased is in your best interests and that of the end user. As this will ensure the equipment sustains a long working life and continues to supply clean, safe water to whomever it serves. We recommend that the equipment is maintained at least once every 12 months.
  • Page 29 Unit 1 Lock Flight Buildings, Wheatlea Industrial Estate, Wigan, Greater Manchester WN3 6XP United Kingdom 9001 : 2015 REGISTERED Membership No. 700106 Certificate No. 185352020 Copyright © 2020 • All Rights Reserved • Flowtech Water Solutions Limited • Company Number: 05125479 • VAT Number: 836 8024 19...

Table of Contents