Ground Bar Kit for FK11/FB11 and FK12/FB12
Installation Guide
2.3 Installing the Ground Bars
After assembling the ground bars, use the following steps to install them in the frequency converter.
1.
Remove 4 screws from the mounting holes in the midplate, 2 from each side of the frequency converter.
Illustration 2: Location of Ground Bar Mounting Holes in Midplate
2.
Position the 2 angle brackets with attached ground bars over the mounting holes in the midplate.
3.
Fasten angle brackets to the midplate with 4 M5x18 mm screws (T25), 2 in each angle bracket.
Tighten to 2.3 Nm (20 in-lb).
4 | Danfoss A/S © 2022.10