First Time Start Up

Coupled Start Up

Jogging and Repeated Starts

2-4 Installation & Operation
Be sure that all power to motor and accessories is off. Be sure the motor shaft is
disconnected from the load and will not cause mechanical rotation of the motor shaft.
1.
Make sure that the mechanical installation is secure. All bolts and nuts are tightened
etc.
2.
If motor has been in storage or idle for some time, check winding insulation integrity
with a Megger.
3.
Inspect all electrical connections for proper termination, clearance, mechanical
strength and electrical continuity.
4.
Be sure all shipping materials and braces (if used) are removed from motor shaft.
5.
Manually rotate the motor shaft to ensure that it rotates freely.
6.
Replace all panels and covers that were removed during installation.
7.
Momentarily apply power and check the direction of rotation of the motor shaft.
8.
If motor rotation is wrong, be sure power is off and change the motor lead
connections. Verify rotation direction before you continue.
9.
Start the motor and ensure operation is smooth without excessive vibration or noise.
If so, run the motor for 1 hour with no load connected.
10. After 1 hour of operation, disconnect power and connect the load to the motor shaft.
Verify all coupling guards and protective devices are installed. Ensure motor is
properly ventilated.
This procedure assumes a coupled start up. Also, that the first time start up procedure
was successful.
1.
Check the coupling and ensure that all guards and protective devices are installed.
2.
Check that the coupling is properly aligned and not binding.
3.
The first coupled start up should be with no load. Apply power and verify that the
load is not transmitting excessive vibration back to the motor though the coupling or
the foundation. Vibration should be at an acceptable level.
4.
Run for approximately 1 hour with the driven equipment in an unloaded condition.
The equipment can now be loaded and operated within specified limits. Do not exceed
the name plate ratings for amperes for steady continuous loads.
Repeated starts and/or jogs of induction motors generally reduce the life of the motor
winding insulation. A much greater amount of heat is produced by each acceleration or
jog than by the same motor under full load. If it is necessary to repeatedly start or jog the
motor, it is advisable to check the application with your local Baldor distributor or Baldor
Service Center.
Heating - Duty rating and maximum ambient temperature are stated on the motor name
plate. Do not exceed these values. If there is any question regarding safe operation,
contact your local Baldor distributor or Baldor Service Center.