Eaton EVER-Tap Installation, Operation And Maintenance Instructions page 43

Voltage regulator
Table of Contents

Advertisement

Table 12 . ADD-AMP capabilities of 50 Hz ratings
Load Current Ratings (A)
Regulation Range (Wye and Open Delta)
± 10%
Regulation Range (Closed Delta)
Rated
Rated
Volts
kVA
± 15%
6600
33
50
66
100
99
150
132
200
198
300
264
400
330
500
396
600
11000
55
50
110
100
165
150
220
200
330
300
440
400
550
500
660
600
15000
75
50
150
100
225
150
300
200
450
300
600
400
750
500
16000
160
100
320
200
22000
110
50
220
100
330
150
440
200
660
300
880
400
33000
165
50
330
100
495
150
333
231
660
200
825
250
a
55/65 °C rise rating on Eaton voltage regulators gives an additional 12% increase in
capacity if the tap-changer's maximum current rating has not been exceeded. For loading
in excess of the above values, please refer to your Eaton representative.
a
± 8.75% ± 7.5%
± 6.25% ± 5%
± 13.1% ± 11.3% ± 9.4%
55
60
68
110
120
135
165
180
203
220
240
270
330
360
405
440
480
540
550
600
668
660
668
668
55
60
68
110
120
135
165
180
203
220
240
270
330
360
405
440
480
540
550
600
668
660
668
668
55
60
68
110
120
135
165
180
203
220
240
270
330
360
405
440
480
540
550
600
668
110
120
135
220
240
270
55
60
68
110
120
135
165
180
203
220
240
270
330
360
405
440
480
540
55
60
68
110
120
135
165
180
203
254
277
312
220
240
270
275
300
338
InstallatIon, operatIon, and MaIntenance InstructIons MN225008EN June 2020
± 7.5%
80
160
240
320
480
640
668
668
80
160
240
320
480
640
668
668
80
160
240
320
480
640
668
160
320
80
160
240
320
480
640
80
160
240
370
320
372
VR-32 and EVER-Tap™ Voltage Regulator