Agency markings
Operating temperature
Storage temperature
Transit temperature
Relative humidity
Operating altitude
Transit altitude
Audible noise
Table 9. Battery
Rack / Tower
configuration
Fuse
Type
Monitoring
Battery port
EBM battery
cable length
Table 10. Communication options
Communication bay
Compatible connectivity
cards
Communication ports
Relay output contacts
Remote On/Off
Remote Power Off
Page 42
CE / C-Tick / cULus
0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of overheating.
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
-25 to 55°C (-13 to 130°F)
0 to 95% no condensing
Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Up to 10,000 meters (32,808 ft) above sea level
< 45 dBA at 1 meter typical
Internal batteries
5000/6000VA: 180Vdc
15 x 12V, 5Ah
63A
Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F).
Lifetime is reduced above 30 °C.
Advanced monitoring for earlier failure detection and warning
External three-pole SBS75G Black connector on UPS for connection to EBM
40cm (15.7in)
(1) available independent communication bay for connectivity cards
Network-MS
Modbus-MS
Relay-MS
RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
Parallel port (DB15): only for 9PX models
(4) relay outputs (normally open or normally closed)
2 pins jumper (normally open)
3 pins jumper (normally open or normally closed)
EBM
9SXEBM180RT, 9PXEBM180: 180Vdc
2 x 15 x 12V, 5Ah
63A