Control Panels
Notice!
Fire walk test includes gas
When you perform a Fire walk test, the security system
tests any 24-hour points that are not invisible, including gas
points.
Performing a walk test:
1. Open the Main Menu.
2. Press Actions to open the menu.
3. Press Test to open the menu.
4. Press Walk Test to open the menu.
5. Press Fire, Intrusion, Service, or Invisible based upon the type of
walk test you wish to perform.
6. The keypad shows the number of points remaining to test. Press
View untested points.
7. Use
/NEXT to go through your desired point and view the status
of that point.
8. Escape from the menu.
Automatic termination
The Walk Test automatically ends after 20 minutes of no test activity.
The keypad sounds during the last 5 minutes of the test.
Bosch Security Systems B.V.
B94x/B93x Actions menu | en
2019.06 | 07 | F.01U.307.371
71