insTallaTion
Gas Venting Requirements — General
1

General Gas Venting Information

The 94 boilers operate with positive overfire pressure.
Adjust the damper assembly during burner start-up to
achieve 0 1" W C positive pressure at damper sample
hole See page 51 for more information
2

Engineered Vent System

WARNING
!
Conventional Category I flue pipe should not
be used as it could leak flue gases, carbon
3
monoxide emissions, and acidic condensate
through seams and joints, which can result in
severe personal injury or death.
Table 12
Technical data for sizing engineered vent system
4
Input
Boiler
Model
BTU/hr
1494
4550
5
1594
4900
1694
5250
1794
5600
1894
5950
1994
6300
2094
6650
6
2194
7000
2294
7350
2394
7700
2494
8050
2594
8400
7
*Based on the unit operating at nominal conditions This value can vary based on the installation location and the operating conditions
8
44
Stack / Vent
Typical Flue
Flow Rate*
Temperature*
CFM
°F
1511
365-385
1627
365-385
1743
365-385
1859
365-385
1976
365-385
2092
365-385
2208
365-385
2324
365-385
2440
365-385
2557
365-385
2673
365-385
2789
365-385
sTeam series
94
The vent system for a Category I or III model
94 steam boiler is considered a designed and
engineered vent system This system should
be designed by a professional using accepted
engineering practices in accordance with local
authority having jurisdiction
See Table 12 for technical data for an engineered
vent system Weil-McLain recommends contacting
your preferred vent supplier to provide design
support
Natural Gas Chart
Damper
Assembly Port
Category I
Pressure
Inches W C
Inches W C
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
0 1
-0 1 to 0
boiler manual
4
Boiler Flue
Category III
Collar
Diameter
Inches W C
Inches
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
0 to 0 1
20
Vent Connection
and Minimum
Vent Diameter
Inches
18
18
18
20
20
20
20
20
22
22
22
22
550-100-157/0523