Baffle Assembly And Installation; Boiler Baffle System - Weil-McLain 4 Series Manual

Steam boiler
Hide thumbs Also See for 4 Series:
Table of Contents

Advertisement

insTallaTion

Baffle Assembly and Installation

1

Boiler Baffle System

The 94 Series 4 baffle system is a combination of two
types of baffles. The first baffle type is for the two 2nd
flue-ways (outer), and the second baffle type is for the
two 3rd flue-ways (inner). See Figure 23. The flue-
2
way doors can only be opened one at a time. Baffle
assembly and installation starts on either side of the
boiler, then repeated on the other side of the boiler
2nd flue-ways (outer):
A telescoping-style, elongated C-channel is inserted
3
into the 2nd flue-ways across the third side fins from
the bottom See Figure 25, page 33.The 2nd flue-
way baffle is designed to extend 5" for every 6"-wide
intermediate section of the boiler. This baffle comes
with hardware (two sheet metal screws, and either
four or eight clevis pins) to telescope the mating
4
Figure 22 C-channel lengths for 2nd flue-way
5
80"
75"
70"
65"
60"
6
7
1494
1594
1694
1794
1894
Connect the C-channel pieces through the four holes shown within
each of the rectangular boxes above with four clevis pins.
8
32
115"
110"
105"
100"
95"
90"
85"
1994
2094
2194
2294
2394
2494
2594
sTeam series
94
C-channel parts into the proper length for each boiler
size See Figure 22 and Table 9
3rd flue-ways (inner):
Left-hand and right-hand sub-assemblies are
assembled together in the 3rd flue-ways to create a flat,
rectangular plate assembly See Figure 29, page 36
The assemblies are created in combinations of four,
five, or seven rectangular plates at the center of each
intermediate casting These groups are connected
together by four side rails to ensure a rectangular plate
is at the center of each intermediate casting for the
entire length of the boiler
Each boiler size has a unique width of rectangular
plate Thus, the right-hand and left-hand sub-
assemblies come with a range of connection holes
to create the proper width of baffle for the boiler size.
See Table 9 and Figure 27, page 35
Table 9
Boiler Size
Always connect in the
same four holes of the
16-hole C-channel.
1494
1594
1694
1794
1894
1994
2094
2194
2294
2394
2494
2594
Figure 23 Front view of completed baffle
Connect through the
bottom four holes.
230138
2nd flue-way
boiler manual
4
Baffle length and width chart
2nd Flue-Way Baffle
3rd Flue-Way Baffle
Length (inches)
Width (inches)
60
65
70
75
80
85
90
95
100
105
110
115
assembly
3rd flue-way
3rd flue-way
3rd flue-way baffle width
550-100-157/0523
4 4
4 2
3 9
3 6
3 4
3 1
2 8
2 6
2 3
2 0
1 8
1 5
2nd flue-way
230145