2.4 Oil Level Safety Switch

An oil level safety switch must be installed in the sump of
the oil separator or the oil reservoir, depending on the
system design. Carlyle recommends an oil level safety
switch that interrupts compressor operation if oil levels
are below adequate levels. Enough oil should remain in
the sump when the switch is opened for the compressor
to operate for at least one minute before completely run-
ning out of oil.
To reduce the possibility of false oil level alarms, Carlyle
recommends that the oil level safety switch should be
open continuously for 5 seconds prior to initiating com-
pressor shutdown.
16
Table 6 — Oil Separators
PART NUMBER
MINIMUM OIL CHARGE
8BSB000704
8BTB000705
8BVB000787
8BSB000643
8BTB000644
KH31ZZ212

2.5 Oil Filter

Provisions should be made to isolate the oil filter using
some combination of shutoff valves and/or check valves.
This will allow for the filter element to be replaced without
removing or isolating the charge in the unit.
Because of the long bearing life requirements, filtration
for this compressor is very stringent. The Beta Ratio for
this filter is greater than or equal to 200 for a five micron
particle size evaluated using ISO 16889 (
Filter areas must also be sufficient to avoid premature
clogging of the filter during normal operation. The Carlyle
supplied filters have a filtration area of > 5000 cm
alarm in the controls should be signaled any time the
pressure drop across the filter (P
exceeds 2 bar (29 psid) indicating the filter needs to be
replaced.
4.5 gal. (17.0 L)
4.5 gal. (17.0 L)
4.5 gal. (17.0 L)
4.5 gal. (17.0 L)
4.5 gal. (17.0 L)
10.0 gal. (38.0 L)
DISCHARGE CFM
17-150
17-170
15-150
17-170
17-170
30-60
200).