3-1-2 INDOOR UNIT
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
1-1. Setting the Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to
the estimated amount of dust in the air of the room.
if the indication is not required, select "No indication"(03).
Setting Description
Standard
Long interval
Short interval
No indication
1-2. Static pressure
If the applicable static pressure does not match the static pressure mode, the static
pressure mode may be changed to another mode manually.
Select the appropriate static pressure according to the installation conditions.
It is necessary to set up a static pressure mode for each usage of static pressure.
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
Function setting can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
Refer to the wired or wireless remote controller manual for detailed setting information.
Function Number
26
* The range of static pressure is different by model.
For details, see the Fan performance curve of the technical data.
If the setting number in AR12 model is configure to "04 to 30", the operation is the same as that "03".
If the setting number in AR14/18 model is configure to "06 to 30", the operation is the same as that "05".
Moreover, setting number value cannot be set to 32 or more.
(For AR*G12/ 14/ 18LSLAP)
Function Number
11
CAUTION
Setting Value
00
01
02
03
04
05
Standard (10 Pa: 12 type)
31
Standard (15 Pa: 14 ,18 type)
Type name
12 type
14 /18 type
03-04
(
Factory setting)
Setting Value
00
01
02
03
( ... Factory setting)
Setting Description
0
P
a
1
0
P
a
2
0
P
a
3
0
P
a
4
0
P
a
5
0
P
a
Range of static pressure
0 to 30 pa
0 to 50 pa