Fujitsu AU G12LVLB Series Service Instruction page 93

Hide thumbs Also See for AU G12LVLB Series:
Table of Contents

Advertisement

1-6.
Setting the Indoor room temperature sensor switching function (Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
Setting Description
No
Yes
If setting value is "00",
room temperature is controlled by the indoor unit temperature sensor.
If setting value is "01",
room temperature is controlled by either indoor unit temperature sensor or remote control unit sensor.
1-7.
Setting the Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
Setting Description
A
B
C
D
1-8 .
Setting the External input control
"Operation /Stop" mode or "Forced stop" mode can be selected.
Setting Description
Operation /Stop mode 1
(Setting forbidden)
Forced stop mode
Operation /Stop mode 2
1-9
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
"Wired remote controller" (01). This function will only work if the function setting 42 is set
at "Both" (01)
Setting Description
Both
Wired remote controller
1-10 Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation
when the outdoor unit is stopped during cooling operation.
Setting Description
Disable
Enable
Remote controller
00 : When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01 : When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02 : Enable or disable this function by remote controller setting.
* When using a 3-wire remote controller, the setting cannot be made by using the remote
controller set to "00" or "01".
(
Factory setting)
Function Number
Setting Value
42
(
Factory setting)
Function Number
Setting Value
44
(
Factory setting)
Function Number
Setting Value
46
(
Function Number
Setting Value
48
(
Factory setting)
Function Number
Setting Value
49
03-06
00
01
00
01
02
03
00
01
02
03
Factory setting)
00
01
00
01
02