Installing the Device
2.5.2 Connecting Low DC Power
6.
Using a #10 ring lug and #10-32 screw, secure the ground terminal on the
power source to the ground connection on the device. Make sure the lug is
tightened to 1.1 N·m (9.5 lbf·in).
Figure 2.7
7.
Install the safety cover over the terminal block.
2.5.2
Connecting Low DC Power
To connect a low DC power supply to the device, do the following:
NOTICE
Electrical hazard – risk of damage to equipment
Do not connect AC power cables to a 12, 24 or 48 VDC power supply terminal block.
Damage to the power supply may occur.
Note
The RUGGEDCOM RX1510 works with both positive VDC power supplies and negative
VDC power supplies.
14
All manuals and user guides at all-guides.com
1
2
#10 Ring Lug
1
#10-32 Screw
2
Connection from External Power Source
3
Ground Connection
4
Ground Connection
3
4
Installation Manual, 04/2021, C79000-G8976-1055-20
RUGGEDCOM RX1510